Environmental Surveillance of Legionella spp. in an Italian University Hospital Results of 10 Years of Analysis

1
Department of Biomedical Sciences, University of Sassari, 07100 Sassari, Italy
2
Department of Medical, Surgical and Experimental Sciences, University of Sassari, 07100 Sassari, Italy
3
University Hospital of Sassari, 07100 Sassari, Italy
*
Author to whom correspondence should be addressed.
Water 2021, 13(16), 2304; https://doi.org/10.3390/w13162304
Submission received: 14 July 2021 / Revised: 18 August 2021 / Accepted: 20 August 2021 / Published: 22 August 2021
(This article belongs to the Section Water and One Health)

Abstract

:
The occurrence of Legionella spp. in the water distribution systems of large hospitals and other healthcare facilities is considered particularly dangerous, due to the critical nature of the hospitalized patients. The aim of this study is to present a pluri-annual environmental surveillance in a large university hospital assessing the prevalence of Legionella spp. and underlining its variability over the years. The samples of water were collected in accordance with the Italian National Guidelines and the sampling sites considered in this study were selected favoring wards with very high-risk patients and with patients at increased risk. The laboratory analyzed a total of 305 water samples deriving from 24 different sampling points. Legionella spp. were detected in 39.4% of samples, the majority of which were contaminated by Legionella pneumophila serogroups 2–14 (68.7%). Statistically significant differences were found among different seasons with a linear trend in positive proportion from summer to spring. Several experimental interventions to prevent and reduce Legionella colonization were attempted, but there is no a definitive method for the complete eradication of this microorganism. The permanent monitoring of hospital water distribution systems is fundamental to preventing the potential risk of nosocomial Legionellosis and to implementing procedures to minimize the risk of Legionella spp. colonization.

1. Introduction

Legionella spp. are Gram-negative waterborne pathogens known to be the causative agents of Legionnaires’ disease, a severe atypical pneumoniae mainly acquired through aspiration of contaminated water, and Pontiac fever, a flu-like syndrome [1,2].
The genus Legionella currently includes 61 species and more than 70 serogroups, of which about half have been recognized as responsible for opportunistic infections in human beings. Legionella spp. are intracellular parasites of freshwater protozoa and they use a similar mechanism to multiply within human phagocyte cells. Legionella pneumophila (L. pneumophila), the most common cause of Legionnaires’ disease cases, is subdivided into 16 different serogroups, of which the serogroup 1 accounts for around 85% of all cases of legionellosis worldwide [3,4].
Legionella, a ubiquitous bacterium commonly found in various aquatic environments, both natural and human-made, can survive for long periods and multiply in low or undetectable numbers. Water systems of large public buildings, households, and industrial plants are suitable environments for the growth and replication of Legionella spp. and other Gram-negative bacteria. If favorable conditions are created (areas of stagnation, parasitism of amoebas, sludge formation), it may result in the acquisition of infection through aspiration of contaminated water or direct inhalation of aerosols [5,6]. The probability of infection depends on the rate of multiplication of bacteria in water installations, the formation of water–air aerosol, as well as the susceptibility of the subject [7].
Particularly dangerous, due to its high lethality, is the occurrence of Legionella spp. in the water distribution systems of large hospitals and other healthcare facilities since these often present several risk factors such as the presence of dead-legs, storage tanks, low flow, and old pipelines. Therefore, water systems represent a potential risk for the hospital population, primarily if Legionella spp. is found in certain wards such as intensive care, hematology, cardiology, hemodialysis, and pulmonology due to the critical nature of patients hospitalized in these units [8,9,10].
According to the latest available data collected by the European Centre for Disease Prevention and Control (ECDC), 10,672 confirmed cases of Legionellosis were reported in 2018, 6% of which were acquired in a hospital [11]. In Italy, in 2019, there were 3199 cases of Legionellosis, 3.8% were hospital acquired [12].
In order to prevent and control Legionella infection sourced from the colonization of water systems, many countries have developed guidelines or regulations. The Italian National guidelines include several concepts in common with other international guidelines, e.g., giving importance to the correct construction and maintenance of water systems, the use of disinfection methods and environmental investigations and the creation of risk assessments for exposure to Legionella. Furthermore, corrective interventions include short-term measures such as replacement of shower heads and taps or long-term measures such as filtration, thermal shock, hyperchlorination, and disinfection with chlorine dioxide [13,14].
Moreover, according to the guidelines of the World Health Organization (WHO) and the recommendations of the European Legionnaires’ Disease Surveillance Network (ELDSNet), especially in healthcare settings, periodic monitoring of the presence of Legionella in the water network in conjunction with control measures is thought to be the most successful preventive approach to avoid possible exposure of patients and health professionals. Proactive environmental surveillance is a useful strategy for preventing nosocomial Legionnaires’ disease [15,16], as well as other nosocomial infections [17,18,19].
In accordance with the Italian National guidelines, in healthcare settings, specific interventions must be planned to ensure the absence of colonization of the air treatment systems and the absence of Legionella (not detectable in relation to the analytical method used and in any case always <100 CFU/L) in the supplied water [14].
The aim of this study is to present a pluri-annual environmental surveillance conducted with the aim to assess the Legionella spp. prevalence in a large university hospital in Sassari (Italy) from 2010 to 2020, underlining its variability over the years and evaluating the potential risk for hospitalized patients and healthcare workers.

2. Materials and Methods

2.1. Study Setting

The study was conducted in the University Hospital of Sassari, the main hospital in Sardinia for the number and heterogeneity of its technological and professional resources (861 beds and 3044 employees). The hospital, which carries out multi-specialist activities of care, teaching, and research for all of northern Sardinia, is comprised of seven pavilions in total.
At the beginning of the 10-years study, a sampling program was prepared which provided for an equal number of samplings every year, at least once a month, even if, due to various contingencies (e.g., restructuring of departments, detection of problems in portions of the water network) some samplings were delayed or more frequently implemented, both between years and between seasons within a specific year.
The laboratory analyzed a total of 170 scheduled samples deriving from 24 different sampling points. Including the control samples carried out following the decontamination procedures performed after the finding of a positive sample, there were 305 water samples (scheduled + control samples). The statistical analysis was performed on the scheduled samples, being all the control samples negative.
The water samplings were performed by a member of the Laboratory of the Hygiene and Hospital Infection Control Operative Unit of the hospital. Sampling sites considered in this study were selected favoring wards with very high-risk patients and with patients at increased risk [14].
The wards analyzed were located in 5 of the 7 hospital pavilions: Gynecology and Obstetrics, Neonatology, Hematology and Operating Rooms (pavilion 2), Intensive Care Unit (pavilion 3), Pulmonology and Operating Rooms (pavilion 4), Infectious Diseases (pavilion 5) and Operating Rooms, Cardioanesthesia, Burn Center and Intensive Care Unit (pavilion 7).

2.2. Sampling

In accordance with the 2015 Italian National Guidelines, the samples of heated water were collected, without running the water, in sterile 1-L bottles containing 0.01% sodium thiosulfate concentration in order to neutralize any residual presence of chlorine [14].
The collected samples were taken to the laboratory and processed within 24 hours according to ISO 11731: 1998 and ISO 11731-2: 2004, in order to be able to compare the results during the years of the study. The 1-L water samples were filtered through sterile membranes of polycarbonate or nylon or nitrocellulose with porosity equal to 0.22 µm or with several membranes in succession if the sample was particularly contaminated. At the end of filtration, the membrane was placed in a closed Falcon container, containing 10 mL of sample water. The detachment of the microorganisms which have been retained was then carried out scraping the membrane by means of glass sticks. After a vigorous stirring with the vortex, the samples obtained represented the concentrate to be used for inoculation.
To minimize the growth of other microbial flora, the concentrated samples were divided into three aliquots: inoculum without treatment, inoculum with heat treatment for 30’ ± 1 at 50 ± 2 °C in an oven, and inoculum with acid treatment in which 1 mL of sample was centrifuged at 3000× g for 30’. Half of the supernatant was removed and 0.5 mL of a solution of HCl-KCl at pH 2.2 ± 0.2 was added to the other half, leaving it at room temperature for 5’. The samples were then sown (0.1 mL) distributing them homogeneously with a sterile spatula. They were then incubated at 36 ± 1 °C in a thermostat, in a humid environment with an atmosphere enriched with CO2 for 10 days.
The suspected colonies were isolated and confirmed as Legionella spp. after verifying the presence of growth on a BCYE (buffered charcoal yeast extract) plate with cysteine and their inability to grow on the culture medium without cysteine. A significant number of Legionella-positive colonies, at least 10 if suspicious colonies were present, were tested from each plate and then identified as L. pneumophila serogroup 1, L. pneumophila serogroups 2–14, or other Legionella species implicated in human diseases using the latex agglutination test (Legionella Latex Test, Oxoid Ltd., Cheshire, UK).
The number of Legionella was derived from the count of the highest number of bacteria observed in the three samples into which we divided our concentrate and results were presented as the number of colony-forming units (CFU) of Legionella per liter (L). Their absence was denoted with the statement “not found”. Samplings were divided into three groups according to the latest national guidelines: (1) 100–1000 CFU/L; (2) 1001–10,000 CFU/L; (3) > 10,000 CFU/L. Samples with a bacterial load lower than 100 CFU/L were not taken into consideration as no intervention was required.
In the event of contamination, in compliance with the Italian National Guidelines, the colonized pipeline was immediately subjected to decontamination procedures and then resampled after 1 and 3 months. Remedial actions, in accordance with ELDSNet recommendations, were thermal shock treatment at 70–80 °C and hyperchlorination.
In accordance with the Italian National Health Institute Technical Report, water temperature and residual chlorine of the sample were determined at the time of collection [20]. The samples were also searched for Pseudomonas aeruginosa as it is believed there is a negative correlation with the finding of Legionella [21].
In this latter case, the sampling, generally equal to 250 mL, was carried out after fluxing the water to check the contamination of the system. Then, in accordance with the UNI EN 12780: 2002 standard, we proceed with filtration of a portion of the sample with a 47-mm diameter cellulose ester membrane with filtration characteristics equivalent to a nominal pore diameter of 0.45 μm. The membrane is placed on the surface of the selective medium Cetrimide Agar and, after incubation at 36 ± 1 °C for 40–48 hours, typical colonies are counted and confirmed. Blue-green colonies that produce pyocyanin are considered confirmed.
The RT-PCR analysis was performed by iQ-CheckTM Quanti Legionella spp., according to the manufacturer’s instructions (Bio-Rad Laboratories, Inc., Hercules, CA, USA).

2.3. Statistical Analysis

The collected data were archived in a specific database. Results were calculated in terms of percentage positivity of the water outlets which tested positive for Legionella. The W Shapiro-Wilk test was used to assess normality of distribution of the analyzed quantitative parameters. Differences among proportions of positive samples calculated for each tertile in relation to water temperature and residual chlorine were tested with z test. Linear trend in proportions (Mantel-Haenszel extension of the chi-square test for trend) was tested, too. Positivity rates were compared using the Chi-squared test. Cuzick’s nonparametric test was used to study the trend across ordered groups. Results were considered statistically significant at p ≤ 0.05. The statistical computations were performed using STATA 16 (StatCorp., Austin, TX, USA).

3. Results

During the 10-years-study, the laboratory analyzed a total of 305 water samples representing 24 different sampling points from wards with very high-risk patients and with patients at increased risk. Excluding the control samples carried out following the decontamination procedures, there were 170 scheduled analyses. Among these, Legionella spp. were detected in 67 samples (39.4%); L. pneumophila was present in 61 samples, which accounted for 91.0%.
Of all samples, 7 (10.5%) were simultaneously positive for different Legionella serotypes. The study showed that in 50.8% (n = 34) of water samples the levels of L. pneumophila were 100–1000 CFU/L, while in 29 samples (43.3%) the levels were 1001–10,000 CFU/L; only a small number of water isolates (n = 4) exceeded 10,000 CFU/L (Table 1).
In particular, as shown in Figure 1, the majority of the positive water samples were contaminated by L. pneumophila serogroups 2–14 (68.7%), whereas L. pneumophila serogroup 1 accounted for 17.9%; a percentage of samples (14.9%) was positive for other Legionella spp.
The highest number of L. pneumophila were detected in the operating room (60,000 CFU/L) and in the intensive care unit (38,000 CFU/L) posing a risk for nosocomial infection and indicating that legionellosis might be a common cause of pneumonia in these settings, as these patients undergo intubation and extubation maneuvers.
Water samples were also analyzed for the presence of Pseudomonas aeruginosa. Although there was no evidence of growth on Legionella positive samples, it was not possible to draw conclusions as only four samples, detected in the intensive care unit and in the operating room, were found to be positive for Pseudomonas aeruginosa.
The majority of Legionella positive samples were detected in 2010 (32.8%), while the lowest percentage was identified in 2016 (3%). There is a rather constant presence of positive samples during the years considered, but a decreasing trend is evident in the most recent years and after the application of the corrective actions (Figure 2).
Statistically significant differences (X2 = 9.549, p = 0.0228) were found among different seasons. The higher rates of isolation of L. pneumophila were observed in May (60.0%) and March (53.8%). Furthermore, in contrast to what emerges in other studies, the lowest percentage of positive samples was found during the summer season (Figure 3) with a statistically significant linear trend in positive proportion from summer to spring (summer 27.9%, autumn 32.7%, winter 41.7%, spring 57.1%) (Z = 2.96, p = 0.003).
The mean temperature for all the samples collected was 39.5 °C (range 12–68 °C), while average residual chlorine was 0.1 mg/L (range 0.02–0.47). Despite the low chlorine content found in all samples, no sample above 0.2 mg/L was found positive for Legionella spp. According to the Italian National Guidelines, the residual chlorine concentration at the distal points of the water supply must remain within the range of 0.5–1.0 mg/L, while according to the Legislative Decree that establishes the standards of drinking water (D.Lgs. n. 31/2001), to which we comply, it must be higher than 0.2 mg/L.
Regarding the chemical and physical parameters of the water samples, we divided the temperature and residual chlorine ranges found during the sampling into tertiles (1st tertile ≤ 32.0 °C; 2nd tertile = 32.1–47.2 °C; 3rd tertile ≥ 47.3 °C). A statistically significant trend of decrease in positivity with increasing temperature was detected, while for the residual chlorine no statistical significance was shown. In particular, as regards temperature, the proportions of positive samples were 63.9% for the first tertile, 47.1% for the second tertile, and 5.3% for the third tertile (p < 0.05) (Figure 4).

Experimentation of Corrective Interventions

During the 10 years in which the study was carried out, several experimental interventions to prevent and reduce Legionella colonization were attempted. One of these methods consisted in the application, in 2015, of sterile disposable filters (Pall Corporation, Port Washington, New York, USA), equipped with a 0.2-μm membrane, to the dispensing taps of five different sampling points. The investigations carried out following the application of these filters demonstrated, both with cultural examination and with real-time PCR, their effectiveness in reducing the high bacterial load detected at time zero, showing neither bacterial growth nor DNA of the microorganism. Filters can therefore be an essential element in reducing Legionella spread by colonized pipelines. However, in view of their routine adoption, a careful evaluation of the economic aspect is necessary. Moreover, the water must be suitably pre-filtered as otherwise the filters become blocked quickly.
Another prevention method adopted was a device (Quantum Hospital Freebioenergy-QHFBE) which, operating with electromagnetic waves, is able to create a volumetric sphere with a radius of 60 m within which the flow of the water in the system improves, increasing the internal surface and decreasing the surface tension by about 20%. The instrument, through a negative ionization of the water, is able to physically transform the limestone (CaCO3) into an allotropic form which greatly reduces the new encrustations of the thermo-hydraulic systems, cleaning, within a few weeks, even the old encrustations [22]. The quantum device was applied at a point considered significant within the hospital’s complex water network that could allow the greatest possible distribution of water to be achieved. After the start of treatment in 2012, three sampling points have been identified and monthly samplings were performed for approximately a year. To facilitate the collection and management of the information acquired, a specific data collection form has been prepared which reports the environmental variables observed during the sampling and the results obtained. The preliminary results, as can be seen from Figure 2, suggested a decrease in positive samples of Legionella of between 60% and 37%. As part of a broader Water Safety Plan process, the results obtained with these methods have been very encouraging and it is believed that, if combined with the classic prevention procedures, they can significantly reduce the presence of Legionella and the related risk of infection. Unfortunately, the high costs associated with the management of the device did not allow a constant or repeated application of this tool over time.

4. Discussion

Legionella spp. have their natural habitat in freshwater environments, where they occur in relatively low numbers. However, industrialization has made it possible for them to colonize hot and cold water pipelines in residential buildings, hospitals, and hotels, where they can reproduce owing to the presence of biofilm in the inner walls of the pipes. In hot water distribution networks, a temperature ranging from 20 °C to 45 °C is the optimum temperature for the replication of these bacteria. Further favorable factors facilitating the colonization of water distribution systems are the lengths and the winding formats of the pipelines, the presence of dead legs with water stagnation, corrosion, and biotic factors (presence of other microorganisms, biofilm) [23]. Frequently, the colonization of a water system by Legionella is the result of an incorrectly designed system, the use of inappropriate materials, and improper maintenance of the water system [24,25].
The results of the present study identified that 39.4% of the analyzed water samples were positive for Legionella spp. It is difficult to make comparisons with the findings reported in the literature resulting from other studies conducted in Italian hospitals as some results are considerably higher [26], while others are substantially similar [27] or lower [28]. Despite this, according to various international environmental surveys, hospital water systems have shown a significantly high percentage of colonization by Legionella [29].
Almost all Legionella isolates were L. pneumophila (91.0%), with most belonging to serogroups 2-14 (68.7%). This is congruent with the fact that L. pneumophila strains from environmental samples have been reported to belong mainly to the pooled serogroups 2–14, in contrast to clinical isolates which are almost exclusively serogroup 1 [30]. On the contrary, in other countries, the most commonly isolated serogroup of L. pneumophila is the serogroup 1 [31]. In 50.8% of water samples collected in this study the levels of L. pneumophila were 100–1000 CFU/L, in 43.3% of samples 1001–10,000 CFU/L levels were detected, and 5.9% of samples had levels of L. pneumophila higher than 10,000 CFU/L.
The present study shows an association between L. pneumophila levels and hot water temperature; the increase in water temperature is linked to the decrease in the number of bacteria. Similarly, the same results were obtained by other researchers [32,33]. The influence of temperature has been identified not only on the survival, but also on the virulence of Legionella [34].
Otherwise, no statistically significant correlation was found for residual chlorine. In this regard we can assume that the low levels of residual chlorine are not totally attributable to a low concentration in the distributed water since the contamination inside the network could have led to an increased reactivity of the chlorine with the organic substances present in the network. Moreover, there was seasonal variability in the positive samples with a statistically significant linear trend in positive proportion from summer to spring, even though recent studies suggest that Legionnaires’ disease occurs most frequently in summer [35,36,37].
The presence of Legionella in water systems poses a potential risk of infection for humans, especially for hospitalized patients, considering that, the infective dose has not yet been precisely identified [38,39]. According to the estimated data, the disease may occur sporadically if the water contamination by Legionella is 1001–10,000 CFU/L, while Legionnaires’ disease can be expected when the number exceeds 10,000 CFU/L [1,32]. However, despite the level of water contamination, once the pipeline has been contaminated there is a latent risk of illness due to the presence of a source of infection.
As the Italian National guidelines suggest, the hospital authorities adopted remedial interventions whenever the bacterial load exceeded the limits and the sample points corresponding to water contaminated by Legionella spp. were subjected to hyper-chlorination and equipped with water heaters and then resampled after 1 and 3 months. Considering that, at present no biocide disinfection methods guarantee the complete eradication of Legionella spp. in water systems, several possible interventions were attempted during the study period. These included the application of antibacterial filters to taps and the use of a gravitational magnetic wave emission device (Quantum). Following the application of these corrective actions there were reductions in trends especially after the use of Quantum in 2012 and until reaching the lowest peak after the use of filters in 2015 (Figure 2). Although these systems have made it possible to detect a certain improvement in the reduction of Legionella, their availability was discontinued due to the economic cost involved.
To prevent and reduce Legionella colonization and nosocomial cases of legionellosis, national and international guidelines recommend environmental surveillance along with remedial measures to control Legionella spp. water contamination. In accordance with the World Health Organization (WHO), one of the best approaches to assessing the health risks associated with Legionella colonization is the development of a water safety plan (WSP). This is a dynamic tool that identifies the risks and dangers involved in the colonization of water systems and indicates the most appropriate control measures as well as the possible obstacles to their implementation [40].
In Sardinia, due to the water characteristics, there is a strong variability in the quality of water supplied, as reported by the authors for various parameters [41,42,43]. For this reason, we currently carry out checks on the potability of the distributed water on a monthly basis. Moreover, a system of additional disinfection units based on chlorine dioxide is being installed in each hospital pavilion at our university hospital.
In our study, despite the number of Legionella isolated over 10 years of constant environmental surveillance, no hospital-acquired cases have been recorded. This may suggest that clinical surveillance was, in fact, not carried out properly, possibly because physicians are unaccustomed to considering Legionella as a possible cause of nosocomial pneumonia. Consequently, it can be argued that there may still be a considerable number of undocumented cases of Legionella infections in our hospital settings. However, in various prospective studies the identification of Legionella colonization led to the identification of hospital-acquired legionellosis [44,45].
Although this study highlights continuous environmental surveillance as a strong point, some limitations are present. First, the impossibility of showing data prior to 2010 as the surveillance was unsystematic due to the lack of national and international guidelines in that period. Second, since no cases of hospital-acquired pneumonia have been recorded, it was not possible to determine a link between the isolation of Legionella and nosocomial pneumonia.

5. Conclusions

This study underlines the importance of the permanent monitoring of hospital water distribution systems to prevent the potential risk of nosocomial legionellosis and to implement procedures to minimize the risk of Legionella spp. colonization. Since many recent studies recommend concurrent research on air to increase the probability of finding Legionella [46,47], it will be important in the future to increase the sensitivity of surveillance by introducing this type of research as well.
Numerous disinfection measures for the eradication of Legionella spp. are available, such as heat and flush, hyper-chlorination and point-of-use filters, but there is no a definitive method for the complete eradication of this microorganism [48,49,50,51]. However, to evaluate the efficacy of any disinfection method, monitoring over a prolonged period is required. Furthermore, active clinical surveillance might substantiate the evidence of its role as a potential nosocomial pathogen in a hospital environment.
Based on our findings, we have promoted awareness to formulate Legionella risk management in our university hospital and advised physicians to recommend Legionella diagnostic testing for patients with suspected nosocomial pneumonia. Indeed, underdiagnosed hospital-acquired Legionnaires’ disease may become evident as the awareness of clinicians increases.

Author Contributions

Conceptualization, G.D., M.D., P.C., and A.A. (Antonio Azara); data curation, G.D., A.A. (Antonella Arghittu), M.D., M.D.M., M.G.D., A.P., and M.R.M.; formal analysis, G.D., P.C., and A.A. (Antonio Azara); investigation, A.A. (Antonella Arghittu), M.D.M., and M.G.D.; methodology, G.D., M.D., and P.C.; software, P.C.; supervision, P.C. and A.A. (Antonio Azara); validation, A.A. (Antonio Azara); writing—original draft, G.D., A.A. (Antonella Arghittu), M.D.M., M.G.D., A.P., M.R.M., P.C., and A.A. (Antonio Azara); writing—review and editing, G.D., M.D., P.C., and A.A. (Antonio Azara). All authors have read and agreed to the published version of the manuscript.

Funding

This study was supported by “Fondo di Ateneo per la Ricerca 2020”, University of Sassari.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The data presented in this study are available on reasonable request from the corresponding author.

Acknowledgments

The authors would like to thank Emma Dempsey for the English Language revision.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Bartram, J.; Yves, C.; Lee, J.V.; Pond, K.; Surman-Lee, S. Legionella and Prevention of Legionellosis; World Health Organization: Geneva, Switzerland, 2007. [Google Scholar]
  2. Brady, M.F.; Sundareshan, V. Legionnaires’ Disease. StatPearls, Treasure Island (FL): StatPearls Publishing; 2021. Available online: https://www.ncbi.nlm.nih.gov/books/NBK430807/ (accessed on 22 August 2021).
  3. Edelstein, P.H.; Cianciotto, N.P.  Legionella. In Mandell, Douglas, and Bennett’s Principles and Practice of Infectious Diseases, 6th ed.; Mandell, G.L., Bennet, J.E., Dolin, R., Eds.; Elsevier: Philadelphia, PA, USA, 2005; pp. 2711–2724. [Google Scholar]
  4. Fields, B.S.; Benson, R.F.; Besser, R.E. Legionella and Legionnaires’ disease: 25 years of investigation. Clin. Microbiol. Rev. 2002, 15, 506–526. [Google Scholar] [CrossRef] [Green Version]
  5. Istituto Superiore di Sanità. Rapporto Annuale Sulla Legionellosi in Italia nel 2018. Available online: http://www.legionellaonline.it/Not%20ISS%20nov%202019.pdf (accessed on 14 July 2021).
  6. Fields, B.S. Legionella in the environment. In Legionella pneumophila. Pathogenesis and Immunity; Hoffman, P., Friedman, H., Bendinelli, M., Eds.; Springer: New York, NY, USA, 2007; pp. 85–94. [Google Scholar]
  7. Legionella: Human Health Criteria Document; Environmental Protection Agency: Richland, WA, USA, 1999.
  8. Lanternier, F.; Ader, F.; Pilmis, B.; Catherinot, E.; Jarraud, S.; Lortholary, O. Legionnaire’s disease in compromised hosts. Infect. Dis. Clin. 2017, 31, 123–135. [Google Scholar] [CrossRef]
  9. Spagnolo, A.M.; Cristina, M.L.; Casini, B.; Perdellim, F. Legionella pneumophila in healthcare facilities. Rev. Med. Microbiol. 2013, 24, 70–80. [Google Scholar] [CrossRef]
  10. Triassi, M.; Di Popolo, A.; Ribera D’Alcala, G.; Albanese, Z.; Cuccurullo, S.; Montegrosso, S.; Crispino, M.; Borella, P.; Zerrilli, R. Clinical and environmental distribution of Legionella pneumophila in a university hospital in Italy: Efficacy of ultraviolet disinfection. J. Hosp. Infect. 2006, 62, 494–501. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  11. Legionnaires’ Disease. Annual Epidemiological Report for 2018. European Centre for Disease Prevention and Control. Available online: https://www.ecdc.europa.eu/sites/default/files/documents/AER_for_2018_Legionnaires.pdf (accessed on 14 July 2021).
  12. Rota, M.C.; Caporali, M.G.; Bella, A.; Scaturro, M.; Giannitelli, S.; Ricci, M.L. Il sistema di Sorveglianza della Legionellosi in Italia: I risultati del 2019. Boll. Epidemiol. Naz. 2020, 1, 32–38. [Google Scholar]
  13. European Society of Clinical Microbiology and Infectious Diseases. European Technical Guidelines for the Prevention, Control and Investigation of Infection Caused by Legionella Species. Available online: https://www.escmid.org/fileadmin/src/media/PDFs/3Research_Projects/ESGLI/ESGLI_European_Technical_Guidelines_for_the_Prevention_Control_and_Investigation_of_Infections_Caused_by_Legionella_species_June_2017.pdf (accessed on 14 July 2021).
  14. Linee Guida per la Prevenzione ed il Controllo della Legionellosi. Available online: https://www.salute.gov.it/imgs/C_17_pubblicazioni_2362_allegato.pdf (accessed on 14 July 2021).
  15. Marchesi, I.; Marchegiano, P.; Bargellini, A.; Cencetti, S.; Frezza, G.; Miselli, M.; Borella, P. Effectiveness of different methods to control Legionella in the water supply: Ten-year experience in an Italian university hospital. J. Hosp. Infect. 2011, 77, 47–51. [Google Scholar] [CrossRef]
  16. Lin, Y.E.; Stout, J.E.; Yu, V.L. Prevention of hospital-acquired legionellosis. Curr. Opin. Infect. Dis. 2011, 24, 350–356. [Google Scholar] [CrossRef]
  17. Deiana, G.; Dettori, M.; Masia, M.D.; Spano, A.L.; Piana, A.; Arghittu, A.; Castiglia, P.; Azara, A. Monitoring Radon Levels in Hospital Environments. Findings of a Preliminary Study in the University Hospital of Sassari, Italy. Environments 2021, 8, 28. [Google Scholar] [CrossRef]
  18. Masia, M.D.; Dettori, M.; Deriu, M.G.; Soddu, S.; Deriu, M.; Arghittu, A.; Azara, A.; Castiglia, P. Microbial Monitoring as a Tool for Preventing Infectious Risk in the Operating Room: Results of 10 Years of Activity. Atmosphere 2021, 12, 19. [Google Scholar] [CrossRef]
  19. Gugliotta, C.; Deiana, G.; Dettori, M.; Sotgiu, G.; Azara, A.; Castiglia, P. Prevalence study on health-care associated infections and on the use of antimicrobials carried out with the light protocol of the European Centre for Disease Prevention and Control. Ann. Ig. 2020, 32, 1–11. [Google Scholar]
  20. Ottaviani, M.; Bonadonna, L. Metodi analitici di riferimento per le acque destinate al consumo umano ai sensi del D.Lgs. 31/2001. Metodi chimici. Rapporti ISTISAN 07/31. 2007; p. 328. Available online: https://www.salute.gov.it/imgs/C_17_pubblicazioni_2277_allegato.pdf (accessed on 22 August 2021).
  21. Paranjape, K.; Bédard, E.; Whyte, L.G.; Ronholm, J.; Prévost, M.; Faucher, S.P. Presence of Legionella spp. in cooling towers: The role of microbial diversity, Pseudomonas, and continuous chlorine application. Water Res. 2020, 169, 115252. [Google Scholar] [CrossRef]
  22. Atena. Quantum’s Technology. Available online: https://www.atena.srl/home-en (accessed on 8 August 2021).
  23. Leoni, E.; De Luca, G.; Legnani, P.P.; Sacchetti, R.; Stampi, S.; Zanetti, F. Legionella waterline colonization: Detection of Legionella species in domestic, hotel and hospital systems. J. Appl. Microbiol. 2005, 98, 373–379. [Google Scholar] [CrossRef] [Green Version]
  24. Breiman, R.F.; Butler, J.C. Legionnaires’ disease: Clinical, epidemiological, and public health perspectives. Semin. Respir. Infect. 1998, 13, 84–89. [Google Scholar]
  25. Leiblein, T.W.; Tucker, M.; Ashall, M.; Lee, S.B.; Gollnisch, C.; Hofer, S. Legionella and risk management in hospitals-A bibliographic research methodology for people responsible for built environment and facility management. Int. J. Hyg. Environ. Health 2016, 219, 890–897. [Google Scholar] [CrossRef]
  26. Laganà, P.; Facciolà, A.; Palermo, R.; Delia, S. Environmental surveillance of legionellosis within an Italian university hospital-results of 15 years of analysis. Int. J. Environ. Res. Public Health 2019, 16, 1103. [Google Scholar] [CrossRef] [Green Version]
  27. Bertolino, G.; Marras, M.; Sanna, C.; Carrucciu, G.; Schintu, M.; Coroneo, V. Ten-year retrospective analysis of Legionella diffusion in Hospital Water Systems and its serogroup seasonal variation. Adv. Exp. Med. Biol. 2020, 1282, 93–103. [Google Scholar]
  28. Orsi, G.B.; Vitali, M.; Marinelli, L.; Ciorba, V.; Tufi, D.; Del Cimmuto, A.; Ursillo, P.; Fabiani, M.; De Santis, S.; Protano, C.; et al. Legionella control in the water system of antiquated hospital buildings by shock and continuous hyperchlorination: 5 years’ experience. BMC Infect. Dis. 2014, 14, 394. [Google Scholar] [CrossRef] [Green Version]
  29. Sabrià, M.; Mòdol, J.M.; Garcia-Nuñez, M.; Reynaga, E.; Pedro-Botet, M.L.; Sopena, N.; Rey-Joly, C. Environmental cultures and hospital-acquired Legionnaires’ disease: A 5-year prospective study in 20 hospitals in Catalonia, Spain. Infect. Control. Hosp. Epidemiol. 2004, 25, 1072–1076. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  30. Doleans, A.; Aurell, H.; Reyrolle, M.; Lina, G.; Freney, J.; Vandenesch, F.; Etienne, J.; Jarraud, S. Clinical and environmental distributions of Legionella strains in France are different. J. Clin. Microbiol. 2004, 42, 458–460. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  31. Yu, P.Y.; Lin, Y.E.; Lin, W.R.; Shih, H.Y.; Chuang, Y.C.; Ben, R.J.; Huang, W.K.; Chen, Y.S.; Liu, Y.C.; Chang, F.Y.; et al. The high prevalence of Legionella pneumophila contamination in hospital potable water systems in Taiwan: Implications for hospital infection control in Asia. Int. J. Infect. Dis. 2008, 12, 416–420. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  32. Sikora, A.; Wójtowicz-Bobin, M.; Kozioł-Montewka, M.; Magryś, A.; Gładysz, I. Prevalence of Legionella pneumophila in water distribution systems in hospitals and public buildings of the Lublin region of eastern Poland. Ann. Agric. Environ. Med. 2015, 22, 195–201. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  33. Legnani, P.P.; Leoni, E.; Corradini, N. Legionella contamination of hospital water supplies: Monitoring of private healthcare facilities in Bologna, Italy. J. Hosp. Infect. 2002, 50, 220–223. [Google Scholar] [CrossRef] [PubMed]
  34. Hrubá, L. The colonization of hot water systems by Legionella. Ann. Agric. Environ. Med. 2009, 16, 115–119. [Google Scholar] [PubMed]
  35. Borella, P.; Montagana, M.T.; Romano-Spica, V.; Stampi, S.; Stancanelly, G.; Triassi, M.; Neglia, R.; Marchesi, I.; Fantuzzi, G.; Tatò, D.; et al. Legionella infection risk from domestic hot water. Emerg. Infect. Dis. 2004, 10, 457–464. [Google Scholar] [CrossRef]
  36. Azara, A.; Piana, A.; Sotgiu, G.; Dettori, M.; Deriu, M.G.; Masia, M.D.; Are, B.M.; Muresu, E. Prevalence study of Legionella spp. contamination in ferries and cruise ships. BMC Public Health 2006, 6, 100. [Google Scholar] [CrossRef] [Green Version]
  37. Piana, A.; Azara, A.; Sotgiu, G.; Mura, I.; Castiglia, P.; Maida, A. Travel-associated Legionellosis: Emerging illness or epidemiological reality? La Legionellosi associata ai viaggi: Malattia emergente o realtà epidemiologica? Ig. Sanita Pubbl. 2006, 62, 305–318. [Google Scholar]
  38. O’Brien, S.J.; Bhopal, R.S. Legionnaires’ disease: The infective dose paradox. Lancet 1993, 342, 5–6. [Google Scholar] [CrossRef]
  39. Aqua Legion. Where are Legionella Found and What Is an Infectious Dose? Available online: https://www.aqualegion.com/legionella-information-bank/water-risk-assessment-reports-large-portfolios/where-are-legionella-found-and-what-is-an-infectious-dose/ (accessed on 8 August 2021).
  40. World Health Organization. Legionella and the Prevention of Legionellosis. 2007. Available online: https://apps.who.int/iris/bitstream/handle/10665/43233/9241562978_eng.pdf?sequence=1&isAllowed=y (accessed on 14 July 2021).
  41. Dettori, M.; Piana, A.; Castiglia, P.; Loria, E.; Azara, A. Qualitative and quantitative aspects of drinking water supply in Sardinia, Italy. A descriptive analysis of the ordinances and public notices issued during the years 2010–2015. Ann. Ig. 2016, 28, 296–303. [Google Scholar]
  42. Azara, A.; Castiglia, P.; Piana, A.; Masia, M.D.; Palmieri, A.; Arru, B.; Maida, G.; Dettori, M. Derogation from drinking water quality standards in Italy according to the European Directive 98/83/EC and the Legislative Decree 31/2001-a look at the recent past. Ann. Ig. 2018, 30, 517–526. [Google Scholar]
  43. Dettori, M.; Azara, A.; Loria, E.; Piana, A.; Masia, M.D.; Palmieri, A.; Cossu, A.; Castiglia, P. Population Distrust of Drinking Water Safety. Community Outrage Analysis, Prediction and Management. Int. J. Environ. Res. Public Health 2019, 16, 1004. [Google Scholar] [CrossRef] [Green Version]
  44. Goetz, A.M.; Stout, J.E.; Jacobs, S.L.; Fisher, M.A.; Ponzer, R.E.; Drenning, S.; Yu, V.L. Nosocomial Legionnaires’ disease discovered in community hospitals following cultures of the water system: Seek and ye shall find. Am. J. Infect. Control. 1998, 26, 8–11. [Google Scholar] [CrossRef]
  45. Yu, V.L.; Beam, T.R., Jr.; Lumish, R.M.; Vickers, R.M.; Fleming, J.; McDermott, C.; Romano, J. Routine culturing for Legionella in the hospital environment may be a good idea: A three-hospital prospective study. Am. J. Med. Sci. 1987, 294, 97–99. [Google Scholar] [CrossRef]
  46. Montagna, M.T.; De Giglio, O.; Cristina, M.L.; Napoli, C.; Pacifico, C.; Agodi, A.; Baldovin, T.; Casini, B.; Coniglio, M.A.; D’Errico, M.M.; et al. Evaluation of Legionella air contamination in healthcare facilities by different sampling methods: An Italian multicenter study. Int. J. Environ. Res. Public Health 2017, 14, 670. [Google Scholar] [CrossRef] [Green Version]
  47. Pasquarella, C.; Veronesi, L.; Castiglia, P.; Liguori, G.; Montagna, M.T.; Napoli, C.; Rizzetto, R.; Torre, I.; Masia, M.D.; Di Onofrio, V.; et al. SItI working group Hygiene in Dentistry. Italian multicentre study on microbial environmental contamination in dental clinics: A pilot study. Sci. Total Environ. 2010, 408, 4045–4051. [Google Scholar] [CrossRef]
  48. Borella, P.; Bargellini, A.; Marchegiano, P.; Vecchi, E.; Marchesi, I. Hospital-acquired Legionella infections: An update on the procedures for controlling environmental contamination. Ann. Ig. 2016, 28, 98–108. [Google Scholar]
  49. Azara, A.; Muresu, E.; Dettori, M.; Ciappeddu, P.; Deidda, A.; Maida, A. First results on the use of chloramines to reduce disinfection byproducts in drinking water. Ig. Sanita Pubbl. 2010, 66, 583–600. [Google Scholar] [PubMed]
  50. Vincenti, S.; de Waure, C.; Raponi, M.; Teleman, A.A.; Boninti, F.; Bruno, S.; Boccia, S.; Damiani, G.; Laurenti, P. Environmental surveillance of Legionella spp. colonization in the water system of a large academic hospital: Analysis of the four-year results on the effectiveness of the chlorine dioxide disinfection method. Sci. Total Environ. 2019, 657, 248–253. [Google Scholar] [CrossRef] [PubMed]
  51. Allegra, S.; Grattard, F.; Girardot, F.; Riffard, S.; Pozzetto, B.; Berthelot, P. Longitudinal evaluation of the efficacy of heat treatment procedures against Legionella spp. in hospital water systems by using a flow cytometric assay. Appl. Environ. Microbiol. 2011, 77, 1268–1275. [Google Scholar] [CrossRef] [PubMed] [Green Version]
Figure 1. Bar chart showing percentages of Legionella pneumophila (Lp) Sgr. 1, Sgr. 2-14, Sgr. 1, and 2-14, and Legionella spp. (other) detected in each year of our survey.
Figure 1. Bar chart showing percentages of Legionella pneumophila (Lp) Sgr. 1, Sgr. 2-14, Sgr. 1, and 2-14, and Legionella spp. (other) detected in each year of our survey.
Water 13 02304 g001
Figure 2. Trend of the number of positive samples detected during the years considered shown both as absolute numbers (orange bars referred to the left scale) and as a trend of the normalized data (grey line referred to the right scale).
Figure 2. Trend of the number of positive samples detected during the years considered shown both as absolute numbers (orange bars referred to the left scale) and as a trend of the normalized data (grey line referred to the right scale).
Water 13 02304 g002
Figure 3. Distribution of total (blue line) and positive samples (orange line) in the seasons of the year. Data are shown as absolute numbers.
Figure 3. Distribution of total (blue line) and positive samples (orange line) in the seasons of the year. Data are shown as absolute numbers.
Water 13 02304 g003
Figure 4. Proportions of positive samples for each tertile of temperature (1st tertile ≤ 32.0 °C; 2nd tertile = 32.1–47.2 °C; 3rd tertile ≥ 47.3 °C). The dashed blue line shows the decreasing trend of positive samples.
Figure 4. Proportions of positive samples for each tertile of temperature (1st tertile ≤ 32.0 °C; 2nd tertile = 32.1–47.2 °C; 3rd tertile ≥ 47.3 °C). The dashed blue line shows the decreasing trend of positive samples.
Water 13 02304 g004
Table 1. Summary of the results characterizing the contamination of water systems by Legionella spp. in the examined pavilions and in the different sampling points. Positive water samples, divided for the various levels of CFU/L, are presented in whole numbers and percentages.
Table 1. Summary of the results characterizing the contamination of water systems by Legionella spp. in the examined pavilions and in the different sampling points. Positive water samples, divided for the various levels of CFU/L, are presented in whole numbers and percentages.
PavilionsSampling PointsPositive Water SamplesCFU/L
100–10001001–10,000>10,000
Number of Samples%RangeNumber of Samples%RangeNumber of Samples%Range
2718 (28.6%)1055.6100–900738.91200–830015.515,200
315 (17.9%)360.0100–400---240.036,000–38,000
4720 (80.0%)945.0100–9001050.01100–810015.060,000
51----------
7824 (50.0%)1250.0100–8001250.01000–9200---
Total2467 (39.4%)3450.8100–9002943.31000–920045.915,200–60,000
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Deiana, G.; Arghittu, A.; Dettori, M.; Masia, M.D.; Deriu, M.G.; Piana, A.; Muroni, M.R.; Castiglia, P.; Azara, A. Environmental Surveillance of Legionella spp. in an Italian University Hospital Results of 10 Years of Analysis. Water 2021, 13, 2304. https://doi.org/10.3390/w13162304

AMA Style

Deiana G, Arghittu A, Dettori M, Masia MD, Deriu MG, Piana A, Muroni MR, Castiglia P, Azara A. Environmental Surveillance of Legionella spp. in an Italian University Hospital Results of 10 Years of Analysis. Water. 2021; 13(16):2304. https://doi.org/10.3390/w13162304

Chicago/Turabian Style

Deiana, Giovanna, Antonella Arghittu, Marco Dettori, Maria Dolores Masia, Maria Grazia Deriu, Andrea Piana, Maria Rosaria Muroni, Paolo Castiglia, and Antonio Azara. 2021. "Environmental Surveillance of Legionella spp. in an Italian University Hospital Results of 10 Years of Analysis" Water 13, no. 16: 2304. https://doi.org/10.3390/w13162304

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop