Article

Improving Thermal Distribution in Water-Cooled PV Modules and Its Effect on RO Permeate Recovery

1
Departamento de Ingeniería Eléctrica y Electrónica, Instituto Tecnológico de Sonora, 5 de Febrero 818 Sur, Cd. Obregón, Sonora C.P. 85000, Mexico
2
Departamento de Ciencias del Agua y Medio Ambiente, Instituto Tecnológico de Sonora, 5 de Febrero 818 Sur, Cd. Obregón, Sonora C.P. 85000, Mexico
3
School of Chemical and Biomolecular Engineering, The University of Sydney, Sydney, NSW 2006, Australia
*
Author to whom correspondence should be addressed.
Water 2021, 13(2), 229; https://doi.org/10.3390/w13020229
Submission received: 18 December 2020 / Revised: 13 January 2021 / Accepted: 15 January 2021 / Published: 19 January 2021
(This article belongs to the Special Issue Water Systems Using Affordable and Clean Energy)

Abstract

:
Among the most notable emerging hybrid technologies for water treatment are those that combine reverse osmosis (RO) membrane systems with alternative energy sources such as solar photovoltaic (PV). Solar PV modules can enable systems disconnected from the electricity grid, and in some locations can also be used for water heating as photovoltaic-thermal (PVT) units, a process in which water removes heat from the PV module, increasing its electrical generation efficiency. When combined with RO, the higher temperature feed water can increase RO permeate flux, improving recovery but decreasing the rejection of dissolved salts. Although the decrease in efficiency of PV modules at higher temperatures is a well-known issue, this is usually under conditions of uniform temperature. However, the temperature distribution in water-cooled PV modules is usually not uniform and, given the anisotropy of the distribution and electrical connection of the PV cells in the module, this factor has not been the focus of much study. In this context, a PVT unit that focuses on increasing the output water temperature with a high global heat transfer coefficient will not necessarily be the most electrically efficient system. This study experimentally assesses several proposed heat-exchange configurations for PVT systems where the PV modules are cooled by forced convective water flow. A simulation model of PVT performance is then validated and used to predict the productivity of the PVT-RO coupling, both in terms of electrical generation and permeate flux of the hybrid system under different conditions. The results suggest that water-cooled PV modules have several potential applications for off-grid and remote water treatment, as well as water transportation systems.

Graphical Abstract

1. Introduction

In response to growing concerns about the impact of climate change on vital resources, experts have proposed the concept of a water–energy–food security nexus, which is one of the most accepted ways to understand and approach sustainable development [1]. This concept, first introduced at the 2008 World Economic Forum, states that there is an inherent interconnection between these three sectors (water, energy and food), and therefore the actions taken in one of them can have an effect in one or both other sectors [2]. One of the most promising technologies that fall under this framework is renewable energy-powered reverse osmosis (RO) for water desalination. RO can provide fresh water year-round by using alternative water sources, such as seawater or brackish water, helping mitigate the water scarcity problem [3]. However, energy consumption is the main cost driver for RO, representing 44% of operating costs. Large energy requirements coupled with high energy prices raise the cost of RO product water [4], making this process economically unfeasible for many low-income regions.
To reduce the problem of high RO costs, much research has focused on coupling RO desalination plants to different types of renewable energy, such as solar photovoltaic (PV), wind, ocean wave power or hybrid systems [5,6]. Since arid regions experiencing water stress are commonly located in dry climate regions that present high levels of solar irradiation, solar power generation seems a logical technology for this application. Accordingly, solar PV is the most commonly used renewable energy for RO, mainly due to the technical and economic advantages of its installation [7]. For example, Rezk et al. [8] operated a 150 m3 d−1 RO desalination plant powered by solar PV and self-charging fuel cells. They found a 70% cost reduction in comparison with a diesel generation system. Elmaadawy et al. [9] designed a renewable energy system to operate a seawater RO desalination plant powered by photovoltaic-wind-diesel energy and found a 61% net present cost reduction. Mostafaeipour et al. [10] tested and proposed a novel brackish water RO desalination system powered by photovoltaic energy, and found a 21% product water cost reduction. Hence, given recent capital cost reductions for renewable energy and the ability to operate RO systems when energy is available, powering RO desalination plants with renewable energy is likely to decrease operating costs significantly, producing low-cost water for human usage with near-zero emissions.
Although solar PV modules can transform radiant energy from the sun into electricity, their efficiency is relatively low (usually less than 20%), and it decreases with increasing temperature [11]. As a “rule of thumb”, it has been estimated that a solar PV module loses 0.5% of efficiency for each 1 °C increase in temperature [12,13]. Research has been conducted to identify other conditions that may also reduce the efficiency of PV modules, such as non-uniform illumination [14,15] and non-uniform temperature distribution over the module surface, which causes current mismatch and could lead to permanent structural damage due to thermal tensions [16].
Many researchers have obtained positive results by implementing passive and active cooling technologies on PV modules. Siecker et al. [13] provide a comparison between different cooling methods (both active and passive) in terms of minimising the effects of increasing temperature, while trying to improve the performance of PV modules. Active cooling methods usually refer to forced convection, where a cooling fluid is driven by a pump or blower which requires additional energy to operate. On the other hand, passive cooling refers to natural convection, where the flow of cooling fluid is driven by density gradients caused by a temperature difference, so they do not require additional energy to operate. A hybrid solar photovoltaic–thermal (PVT) module cooled by forced water circulation is a common example of active cooling, in which water enters and exits the module at defined locations. These systems have the dual objective of electricity production and water heating. The positions of the inlets and outlets influence the fluid flow inside the heat exchanger, and this is commonly controlled by fixing the flow channels in the heat exchanger design [13,17].
Research shows that the overall energy (thermal + electrical) efficiency of a PV module can be increased to 40% if it is cooled in a PVT arrangement [18]. For PV-RO coupling purposes, the PVT system stands out as one of the best options. It usually consists of a heat exchanger mounted on the back of the PV module, through which a cooling fluid is circulated, removing heat from the silicon cells of the PV module and increasing their electrical generation. This is convenient for PV-RO coupling for two reasons: (a) the RO feed water (e.g., seawater or brackish water) can be used as the circulating fluid, increasing its temperature; (b) the higher temperature feed water can increase RO permeate flux, improving recovery, and therefore generating more product water for a given membrane area, albeit decreasing the rejection of dissolved salts [19]. At the time of writing, there is only one study reporting a RO desalination plant operated with PVT cooling, finding an increased efficiency for PVT due to cooling and fewer required modules [20].
Although the decrease in the efficiency of PV modules at higher temperatures is a well-known issue, this has traditionally been investigated under conditions of uniform temperature. However, temperature distribution in water-cooled PV modules is usually not uniform [16] and, given the anisotropy of the distribution and electrical connection of the PV cells in the module, this factor has not been the focus of much study and is not well understood. In this context, a PVT unit that focuses on increasing the output water temperature with a high global heat transfer coefficient will not necessarily be the most electrically efficient system. Given that important efforts are currently underway to power RO desalination plants with renewable energy, and that increasing the solar energy efficiency of PVT modules is desirable, this study experimentally assesses several proposed heat-exchange configurations for PVT systems where the PV modules are actively cooled by forced convective water flow. Emphasis is made on understanding the flow characteristics that lead to better temperature distribution and larger efficiency gains compared to modules without active cooling. A simulation model of PVT performance is then validated and used to predict the productivity of the PVT-RO coupling, both in terms of electrical generation and permeate flux of the hybrid system under different conditions. The RO simulation assumes a 1D non-isothermal model which calculates the variation in water properties (i.e., density and viscosity based on concentration, pressure, and temperature) along with the membrane permeance at different operating temperatures to predict permeate production. Hence, this paper presents the first study of a RO desalination system operated with PVT cooling which considers the effect of varying temperature at the RO feed. The insights gained are applicable for environmental conditions with high solar irradiation, high ambient temperature and low humidity, such as those in northwest Mexico.

2. Materials and Methods

A PVT module was designed and constructed, incorporating 16 fluid inlets/outlets at distinct locations on the back of the PV module (functioning as a heat exchanger), which are used for cooling via forced convection with water as the cooling fluid. Forced convection (as opposed to natural convection) is selected as the cooling strategy because RO systems already require a pumping system for their operation, so implementing this strategy does not require additional pumping equipment. Nonetheless, forced convection does involve an increase in pressure losses within the heat exchanger on the back of the PV module, which in turn requires more pumping energy. There is therefore a trade-off when implementing forced convection as the active cooling method, i.e., between the additional energy generated from the PV efficiency increase and the additional energy consumption due to pressure losses.
Experimental data is collected by measuring the electrical and thermal performance of the PVT module under two different flow rates (1 and 2 L min−1) and 11 different inlet/outlet heat exchange configurations as described in Appendix A. The collected data is used to validate a numerical model, which is then used to predict the daily water production of a PVT-RO plant under different combinations of flow rate and heat exchange configuration, for distinct weather conditions. Detailed explanations of the experimental and numerical methods employed are described in the following sections.

2.1. Characterisation of the PV Module

Commercial PV modules (AXITEC AC-270-P polycrystalline cells) were used for the experimental tests. Table 1 shows the technical specifications for these modules, according to the manufacturer, at standard test conditions (1000 W m−2 solar irradiation and 25 °C).
The configuration of the PV cells in the module is distributed in 3 groups of 20 cells connected in series. Each group is formed by two columns of 10 cells in series, and the groups are connected in series with each other by means of diodes. This forms a rectangular arrangement of 6 × 10 cells in the panel, as shown in Figure 1. The arrangement of the PV cells is a characteristic that impacts how cooling may affect any efficiency increases, this due to the dependence of electricity generation between the groups. The group with the cell or cells with highest resistance (due to a higher temperature) may activate the bypass diode and will limit the amount of energy produced by the array. Hence, if there is a large temperature gradient, it should theoretically affect the least number of groups if it is aligned with the groups (i.e., in the horizontal direction).
The solar modules are electrically characterised by running a power output test under different electric charging conditions, through the capacitor charging method for an I–V curve tracer [21], as depicted in Figure 2.
This test consists of connecting the PV module to a large capacitor C with a Switch (SW1) and to two sensor probes (A, V), both connected to an oscilloscope. The capacitor is then discharged through a large resistor R by activating SW2 and disconnecting SW1. This cycle is repeated several times for statistical analysis. The data collected from this test are then used to trace the characteristic I-V curve for the PV module. This characterisation was conducted at a solar irradiation value of 1000 W m−2 and an average module temperature of 59.2 °C.
The relationship between the electrical efficiency of the module and its operating temperature is determined experimentally at a uniform temperature and constant solar irradiation. This is achieved by cooling the PV module using ice, distributed over the surface of the panel. The temperature is monitored until it reaches 10 °C; then, the ice and excess moisture are removed, and finally the open circuit voltage and short circuit current of the PV panel are measured. The measurements are continued while the temperature of the panel increases due to the warm ambient conditions, with data collected in triplicate each time an increment of 5 °C is detected.
The electrical efficiency of the PV module is calculated using the Fill Factor (FF), which is the ratio of maximum obtainable power to the product of open circuit voltage and short circuit current. The calculation of the efficiency (η) considers the energy produced with respect to the received solar energy. For this work, the efficiency is determined by:
η = V o c I s c F F G s A P V
where Gs is the solar irradiation, Voc is the open-circuit voltage, Isc is the short circuit current, and APV is the active area of the PV module.

2.2. PVT Module Design

A heat exchanger is adapted into the PV module, consisting of a rectangular enclosure of expanded PVC mounted on the back of the module. This enclosure has the same width and length dimensions as the module (see Table 1), and a proposed thickness of 27 mm. Preliminary calculations indicated that a fluid layer thickness of 50 mm or less would yield better heat exchange between the cooling fluid and the PV module, so the thickness of the aluminium frame was used for simplicity.
The design of the heat exchanger includes 16 valves that can work both as inlets and outlets, to allow experimenting with different configurations of forced convective flow of cooling water. This proposed PVT module design with multiple inlets and outlets and an unobstructed enclosure allows experimental versatility for testing different configurations within the same piece of equipment. This particular design was chosen as opposed to the implementation of fixed defined channels within the exchanger, given that such a design would require a different heat exchanger to be constructed for each configuration. Moreover, the proposed design allows the study of the effect of recirculation zones, as well as the effect of volumetric flow rate of cooling fluid on the flow pattern.
A total of 11 configurations are analysed in this paper in terms of heat removal, electrical generation and pressure drop. The location of the valves is indicated in Figure 3. The 11 analysed configurations are presented in Table 2, and one of them (B4) is graphically depicted in Figure 4 as an example. The graphical representation of the remaining configurations can be found in Appendix A. All the configuration schematics are accompanied by the expected flow lines. As the work presented in this paper does not include fluid dynamics simulations, the flow lines presented in Figure 4 are only for illustrative purposes, and are estimated based on the corresponding experimental thermographic image for each configuration. The configurations are classified into three subgroups, named by the manner in which the fluid enters the heat exchanger: from the bottom (B), from a single valve (S), and laterally (L).

2.3. PVT Module Performance Analysis

To analyse and characterise the thermal and electric performance, each proposed heat exchange configuration is tested in five PVT modules simultaneously while recording the weather conditions in terms of solar irradiation (Gs), wind speed (va), relative humidity (HR), and ambient temperature (Ta). A regular (unmodified) PV module without a cooling system is also tested under the same conditions for comparison purposes. Each configuration test is done under two different cooling water flows (1 and 2 L min−1). The cooling water is obtained from a nearby well, with an average salinity (wb) of 500 ppm. The cooling water temperature is kept constant and all the tests are repeated three times. Figure 5a shows a photograph of the experiment, whereas Figure 5b shows a schematic of the experimental setup: a low-pressure (LP) pump makes water flow from a storage tank to the PVT modules, cooling them as they generate electricity, before it is finally discharged to another storage tank. The variables measured are the electrical power generated (Pe), the temperatures of the PV module (TPV), the water inlet and outlet temperature at the panel (Twi and Two, respectively), the conductivity of the cool water, and the pressure losses across the heat exchanger. The photovoltaic panel operates at maximum power conditions by connecting a micro-inverter to the electrical output of the panel. The micro-inverter injects the generated energy to the power grid, which draws a current and acts as an electrical load.
The environmental conditions (Gs, va, HR and Ta) are monitored by a weather station. The water temperature and salinity at the PVT module inlet and outlet are measured using thermocouples and an electrical conductivity meter, respectively, and the cooling/feed water flow rate (Qw) is manipulated using a bypass valve. The pressure losses are estimated from the total flow rate passing through the LP pump (Qw plus the bypass) using the characteristic curve of the pump as supplied by the manufacturer, shown in Appendix B.
The PV module temperature distribution for each configuration is measured using a thermographic camera (model Flir i5) with a thermal sensitivity of <0.1 °C at 25 °C. The collected temperature data from each thermal image are then normalised, and the median, minimum, maximum, and standard deviation of the temperatures on the module surface are determined from these data. The heat removed from the module by the cooling water (qw) is calculated using the following expression:
q w = ρ w Q w C p w ( T w o T w i )
where ρw and Cpw are the density and heat capacity of the cooling water, respectively. Cooling water properties are estimated using correlations reported by Sharqawy et al. [22] for density, heat capacity [23], and viscosity [24].
The heat removed by the heat exchanger ( q x ) is modelled by:
q x = U A p x Δ T l m
where Apx is the PV module area in contact with the cooling water (the heat exchange area), ∆Tlm is the logarithmic mean temperature difference between the module and the cooling water, and U is the global heat transfer coefficient for the heat exchanger.
It is considered that the heat removed from the module is the only heat absorbed by the cooling water, hence qw = qx, such that U can be obtained using Equations (2) and (3) for each heat exchange configuration:
U = ρ w Q w C p w ( T w o T w i ) A p x Δ T l m
As a non-uniform temperature distribution will lead to a decrease in electrical efficiency [16], we define the efficiency drop (Δη) as the difference between the efficiency expected at the mean temperature of the PV module (ηu) and the measured electrical efficiency under forced convective cooling (ηc):
Δ η = η u η c
The uniform efficiency at the mean temperature (ηu) is estimated from the experimental data obtained following the methodology described in Section 2.1. Finally, the relationship between efficiency drop is correlated to Gs, TPV, U, Qw and the standard deviation of the PV module temperature distribution (σT). The average values of Δη, Qw, U, σT and maximum PVT module temperature (TPV,max) are quantified for each test. These values are compared with a theoretical distribution of probabilities for continuous quantitative variables, using the t-student parametric distribution [25].
A linear regression between the parameters (Qw, U, σT and TPV,max) and the efficiency drop (Δη) is also performed to determine the influence of these parameters on the output performance of the system. This analysis assists in determining which parameter has a stronger effect on the electrical efficiency. If the Pearson correlation coefficient between Δη and either Qw, U, σT or TPV,max is less than −0.7, this would suggest that increasing the value of that parameter would improve the efficiency of the PVT module (by decreasing the efficiency drop), according to factorial simplicity index theory of Kaiser [26].

2.4. PVT-RO Simulation

A mathematical model of the combined PVT-RO system depicted in Figure 6 is implemented in MATLAB (Mathworks). The PVT-RO model (see Figure 7) consists of a solar PVT module, a high-pressure (HP) pump, and a RO membrane module. Some outputs of the PVT model (Qb and Pe) are inputs to the HP pump model that determines the RO feed pressure (p). The RO model then takes inputs from both the PVT and HP pump models to determine the permeate variables (Qp and wp). All models are considered to operate under quasi-steady state, under the assumption that any dynamic changes to the operating conditions (changes in weather, location of the sun, etc.) occur at a slower time scale than necessary to reach thermal equilibrium in both the PVT and the RO modules.

2.4.1. Solar PVT Module

The PVT model consists of a system of non-linear equations, solved using a Newton-Raphson iterative method. The energy balance around the PVT module is given by:
E P V = q s q a q r q x P e o
where EPV is the rate of net energy input into the PVT module, qs is the energy input from solar irradiation, qa is the thermal energy removed by convective heat transfer with the wind, qr is the cooling via radiative heat transfer with the sky, and Peo is the electrical power output of the PVT module. The terms on the right-hand side of Equation (6) are estimated by Equation (3) and by:
q s = ( G b e a m f θ cos θ + G d i f ) α s A P V
q a = h a A p a ( T p T a )
q r = A P V σ ε ( T p 4 T s k y 4 )
P e o = η c A P V ( G b e a m + G d i f )
where Gbeam and Gdif are the beam and diffuse solar irradiation, αs and APV are the solar absorptivity and the active area of the PV module, fθ is the angular dependence of solar absorptance [27], θ is the incidence angle between the PV module and the sun, ha is the wind heat transfer coefficient, Apa is the module area in contact with the wind, σ is the Stefan-Boltzmann constant, Tsky is the sky temperature, and ε is the emissivity of the PV module. Further details and auxiliary expressions used in computing the values used for Equation (7) through Equation (10) are provided in Appendix C.
For the cooling water, the energy balance considers only the heat exchange with the panel that leads to an increase in water temperature, and the sensible heat absorbed by the water as given by Equation (2) The energy balance for the cooling water is then:
E w = q x q w
where Ew is the rate of net energy input into the cooling water. At steady state, both rates of energy input (EPV and Ew) should be equal to zero, leading to a system of two non-linear equations:
E P V ( T p , T w o ) = 0 E w ( T p , T w o ) = 0
These non-linear equations represent the energy balances around the PV module-heat exchanger system (i.e., the PVT module). The weather conditions and the inlet cooling water flow properties are inputs to this system, and the outputs consist of the outlet water flow properties and electrical power (Pe), as depicted in Figure 7.
However, not all of the electrical power generated by the PVT module (Peo) is available for the HP pump. This because a non-negligible amount of power is required to force the flow of cooling water across the PVT heat exchanger. In order to account for this, the low-pressure pumping power (PLP) is estimated as:
P L P = Δ p P V T Q w η L P
where ΔpPVT is the pressure drop across the heat exchanger in the PVT module and ηLP is the energy efficiency of the LP pump (assumed as 75% for a fit-for-purpose pump). The power available for the HP pumps is then taken to be:
P e = P e o P L P

2.4.2. HP Pump

The HP pump mathematical model is a series of multilinear regressions fitted to the technical datasheet of a HP DC pump (SunPumps SIJ 3.1-1500P-225 BL). The inputs to this model are the PV power output (Pe) and the cooling water outlet flow rate (Qwo). The model calculates the maximum water pressure (p) that can be provided by the HP pump to the RO module under those conditions. More details are provided in Appendix C.

2.4.3. RO Membrane Module

The RO modelling in this work largely follows the approach of Toh et al. [28] and Bartholomew & Mauter [29], but with the additional complexity of allowing for the fluid properties (density, viscosity, heat capacity) and membrane properties (water and salt permeance) to vary with temperature as well as with salinity. At its core, the RO model is a combination of two simpler models: a non-linear algebraic equation system for determining the local permeate flux, and a system of non-linear ordinary differential equations (ODEs) describing the evolution of the unidimensional profiles of the variables (flow velocity, concentration, temperature, and pressure) along the membrane module, as depicted in Figure 8. The former is solved via the simple fixed-point iteration method [30], while the latter is solved by a Runge–Kutta type algorithm.
The local volumetric permeate flux (Jv) at each point along the RO membrane module (x‑direction) is estimated using the Kedem–Katchalsky–Merten equation [31]:
J v = Δ p t m ( π m π p ) μ R m
where Δptm is the transmembrane pressure difference between the feed and permeate channels, πm and πp are the osmotic pressure on the feed and permeate side of the RO membrane, μ is the fluid viscosity and Rm is the membrane resistance. The effect of changes in water temperature is explicitly considered to affect the fluid viscosity, as well as the osmotic pressure following the van’t Hoff equation for NaCl:
π = 2 φ R g w ρ T M s
where φ is the osmotic coefficient, Rg is the universal gas constant and Ms is the molar mass of NaCl. The temperature dependence of osmotic pressure is explicit in Equation (16), but it is also implicit as φ and ρ are also considered to be temperature dependent [22]. The effect of temperature on the membrane resistance and salt permeance were determined experimentally for a commercial DuPont BW30 membrane. A non-linear system arises from the coupling of permeate flux and membrane surface salinity (wm) due to the effect of concentration polarisation [28]:
Γ = w m w p w b w p = exp ( J v k m t )
where Г is the concentration polarisation modulus and kmt is the mass transfer coefficient on the membrane surface.
Finally, the model describing the profiles along the membrane module is based on mass and energy balances under steady-state non-isothermal conditions, and neglecting longitudinal dispersion. This results in the following system of ODEs:
d u b d x = 2 J v ρ p h c h ρ b u b ρ b ( ρ b x d w b d x + ρ b x d T b d x + ρ b x d p b d x )
d w b d x = 2 J v ρ p h c h u b ρ b R o b s w b
d T b d x = 2 J v ρ p h c h u b C p , b ρ b ( Δ H s , r R o b s w b + Δ H t m + Δ H p , t m ) Δ H s , r C p , b d w b d x 1 C p , b ρ b ( 1 T b ρ b ρ b T b ) d p b d x
d p d x = 2 ρ u b 2 d h ϵ 2 f
where x is the direction along the membrane module length, the subscript b represents the feed channel bulk conditions, hch is the membrane channel height (taken to be equal to the spacer thickness), ϵ is the feed channel void fraction (the volume other than the spacer mesh), dh is the hydraulic diameter of the spacer-filled feed channel, f is the Fanning friction factor, Robs is the local observed rejection, and ΔHs,r = 66.2 kJ kg1 is the specific enthalpy change of solution for NaCl at reference conditions of Tr = 25 °C and pr = 1 atm. The transmembrane temperature-enthalpy change (ΔHT,tm), and transmembrane pressure-enthalpy change (ΔHp,tm), are respectively defined as follows:
Δ H T , t m = T r T b [ C p ( T ,   w b , p r ) C p ( T ,   w p , p r ) ] d T
Δ H p , t m = p p p b 1 ρ ( T b ,   w b , p ) [ 1 T b ρ ( T b ,   w b , p )   ( p T ) p , w b ] d p
Equations (18)–(21) are integrated along the membrane module length (see Figure 8) to obtain the total permeate flow (Qp) and permeate salinity (wp). Further details regarding the estimation of permeate flow and auxiliary equations are presented in Appendix C.
All simulations assume a quasi-steady state using data from a local weather station in Ciudad Obregon, Mexico (27°29′35.2″ N 109°58′10.7″ W), for summer (24 July 2018), autumn (20 October 2019) and winter (3 January 2020) conditions. The weather data for these dates and location is presented in Appendix D. Three simulation scenarios are considered: Scenario 1 “Without cooling” emulates the electrical generation of a regular PV-RO plant for comparison; Scenario 2 “Continuous cooling” emulates the performance of a PVT-RO plant incorporating the different heat exchange configurations considered in this paper; and Scenario 3 “Max production” selects the best performance out of scenarios 1 and 2 depending on the time of the day and environmental conditions, which results in the maximum possible permeate production for the day under consideration. All scenarios assume the same dimensions and characteristics of the experimental PVT module, and the simulated RO membrane is based on the BW30-8040 DuPont FilmTec module for brackish water [32]. The parameter values considered are summarised in Table 3.
To simulate the behaviour of the PVT-RO system under the different cooling configurations in Scenario 2, the simulation parameters are adjusted to match each heat exchange configuration experimental data as follows: (1) the experimental value of U is used as an input to the PVT model, and (2) the dependency of Δη on the operating conditions (Gs, TPV and Qw) and cooling configuration is incorporated. Moreover, to guarantee that 1 and 2 L min1 are flowing through each of the modules while keeping the same feed flow rate into the RO module (Qb), half of the feed flow rate is assumed to bypass the PV panels at Qw = 1 L min1.

3. Results and Discussion

3.1. PV Module Characterisation

Experimental tests showed that the behaviour of the PV modules varies from the data reported by the manufacturer. This is due to manufacturing defects, so it is recommended to generate a specific I-V curve for the PV panel used under real conditions. A PV module efficiency loss of 0.7% for each 10 °C increase in uniform temperature was observed. Figure 9 shows the I–V curve obtained in the field at TPV = 59.2 °C and Gs = 1000 W m−2. The real efficiency obtained is 16.02%, about 0.58% lower than that reported by the manufacturer (see Table 1).
Regarding the effect of temperature, Figure 10 shows that the electrical efficiency significantly decreases due to increases in temperature. A significant (95% confidence) negative correlation is observed for the relationship between these variables (r = 0.92, p < 0.001). The degree of goodness of fit was high (R2 = 0.85) for the linear regression model:
η u = 0.1777 7.034 × 10 4   T P V
where TPV is the uniform PV module temperature in °C.

3.2. Experimental Results of the PV Module Cooling Configurations

In order to remove the biases and effects introduced by the different environmental conditions at the time of testing each of the different configurations, the temperature distribution for each configuration was first normalised as follows:
T P V , n = T ¯ P V , N C T P V , C T ¯ P V , N C T ¯ P V , C
where the subscript n represents the normalised temperature, NC refers to the module that is not cooled, and C refers to the water-cooled module. The overbars represent the arithmetic mean of the temperature for the corresponding module. Subtracting the temperature of the cooled module from that of the non-cooled module removes some of the bias associated with higher or lower solar irradiation during measurement. By this definition, the normalised temperature should have an arithmetic mean of 1.
With respect to the temperature distribution in the PVT, Figure 11 shows the ranges of normalised temperatures for each heat exchange configuration, indicating the maximum and minimum temperatures, as well as the sizes of the central interquartiles and the median. This information can help determine which configurations lead to a more uniform temperature distribution. Group B has more uniform and compact ranges than groups S and L. Conversely, group S presents the largest ranges of temperatures, particularly configurations S1 and S3.
The L group shows the configuration with the smallest normalised temperature range (L2), although there is more variability in the ranges within the L group, this compared to the B group. The configurations with the smallest normalised temperature range are the ones that lead to a more uniform temperature, being this the condition with Δη close to zero.
The results of the experimental measurements of efficiency drop for the PVT modules are shown in Figure 12. In the graphs in this figure, Δη is plotted against maximum temperature (TPV,max), overall heat transfer coefficient (U) and the standard deviation of the temperature distribution (σT). In addition, the two values of water flow rate (Qw) for each configuration are joined by a line, with a circle indicating the larger flow rate of Qw = 2 L min−1.
Configuration types B, S and L are indicated by similar colour groups in Figure 12. This is done to visualise the similarities between the members of each group. In the case of group B, it can be seen that the configurations are grouped on the lower part of each graph, where Δη is lower and therefore closer to the efficiency of the photovoltaic panel at uniform temperature. This suggests that configurations belonging to group B result in best performance in terms of temperature distribution, leading to lower efficiency drop. It can also be seen in Figure 12b that, for all configurations, increasing Qw reduced the efficiency drop and increased U.
However, Figure 12a,c indicate that a larger temperature range (i.e., a larger TPV,max) or a larger temperature variability (i.e., a larger σT) do not necessarily lead to larger efficiency drops in the configurations tested. This is particularly evident for configurations B1, L2 and L3, for which TPV,max and σT increase as Qw is increased, but Δη is reduced. Nevertheless, if the analysis is focused on the overall data, a general tendency can be seen that Δη is larger for configurations with larger σT and larger TPV,max. On the flipside, this general tendency is not observed for the relationship between Δη and U. These observations are corroborated by the overall Pearson correlation coefficients presented in Table 4, and suggest that, although in general a better temperature distribution and lower temperature range will lead to less efficiency losses, for any particular configuration heat removal drives efficiency drop.
To quantify the trends observed in Figure 12, the statistical relationships between the variables in that figure are presented in Table 4, which shows the Pearson correlation coefficients between the efficiency drop for each configuration and the operating parameters studied, as well as the overall correlations. It can be seen that Qw has a negative correlation with Δη in all configurations and overall. This means that increasing feed flow rate generally led to an increase in electrical efficiency, confirming the trends observed in Figure 12b. Configurations B4, S1, S2, and L2 show a correlation coefficient magnitude ≥ 0.7, which classifies as highly significant behaviour according to the factorial simplicity index.
On the other hand, the heat transfer coefficient (U) did not show a highly significant behaviour in affecting the efficiency drop overall. Although for most configurations an increase in U was slightly correlated with a decrease in efficiency drop (a trend also observed in Figure 12b), the statistical results suggest that increasing heat transfer efficiency will not necessarily lead to higher energy generation. The results of configurations with a positive correlation may be related with the input cooling fluid being distributed vertically with less uniform heat extraction inside the PVT module. Since the cooling fluid residence time is low, this is probably due to the cooling fluid being directed to vertical outlets placed partially aligned with the inputs. The negative signs may be attributed to the fact that the temperature of the cooling fluid is increased more along flow lines with a longer residence time inside the PVT module. This is due to the fact that the direction of the water changes, as inputs are not aligned with outputs, leading to recirculation zones.
As regards the effect of σT on the efficiency drop, the L3 configuration presents a correlation coefficient ≤−0.7 (r = −0.92). This result is probably due to the multiple inlets and outlets being aligned horizontally and the PV cells in the module being wired vertically and in parallel with each other, thus the temperature variation along each series of PV cells is minimal. The negative correlation can be explained by the fact that a higher temperature variability is mostly associated with a larger water temperature increase due to more cooling of the PV module, hence reducing the efficiency drop. On the other extreme, the B3 configuration has a correlation coefficient ≥0.7. This could indicate that the fluid tends flow largely in the vertical direction, resulting in a large temperature difference along the PV cells wired in series, therefore reducing the electrical efficiency in the photovoltaic panel.
The correlation coefficients for TPV,max show that configuration B1 has a highly significant coefficient ≤−0.7 (r = −0.82). This can probably be attributed to the symmetric vertical flow of cooling water. Configurations B3 and L3 also show highly significant correlation coefficients ≥0.7. This is probably because the multiple outlets are geometrically spaced from each other.

3.3. PVT-RO Modelling Results

The experimental data for heat transfer (U) and efficiency drop is incorporated into the PVT-RO model described in Section 2.4. This in order to estimate the energy generated by the PVT modules under different cooling configurations and without forced cooling, as well as the energy available to be used in the RO desalination process (Ee). The model then uses these results to predict the volume of water produced by the PVT-RO hybrid system (Volp) and the salinity of the permeate (wp). Simulation results for two representative dates are presented in Table 5 and Table 6.
The model results for 20 October (Table 5) show that B1 has the best performance of all configurations tested under continuous cooling at Qw = 1 L min1, both in terms of energy and permeate production. For the tests under continuous cooling at Qw = 2 L min1, the energy available is reduced in comparison with the lower flow rate, and therefore the production of permeate water is also reduced. The model results for 24 July (Table 6) also show that B1 results in the best performance for both Qw = 1 L min1 and Qw = 2 L min1.
An important factor to be considered in addition to the amount of water produced is the salinity of the permeate flow, as this has implications in terms of the potential applications for PVT-RO. Observed rejection for all the configurations tested range around 92% to 95% in the summer, when the lowest values are observed. Importantly, the configuration with the largest water production (B1) presents the lowest rejection (92%) and largest permeate salinity (39 ppm) from a feed water salinity of 500 ppm. This is expected, as Figure 12b shows that configuration B1 yields the largest heat transfer coefficient, and hence the highest RO feed water temperature. A higher temperature feed is known to reduce salt rejection as well as increasing water permeance for RO and other osmotic separation membranes [19,34].
Another effect that can be observed in Figure 12 is a lower permeate salinity at the larger cooling water flow rate of Qw = 2 L min1. This effect can be related to the lower available pumping energy at this higher cooling rate. Although in general, for all configurations, operating at the larger flow rate results in a lower efficiency drop (see Figure 13), the larger pressure drop across the PVT heat exchanger results in less energy available (Ee) for the RO HP pump. This in turn leads to a lower operating pressure for the RO module, which results in a lower permeate flux, but also in less concentration polarisation as predicted by Equation (17). This latter effect also leads to a lower membrane surface salinity, and thus less salt passage through the RO membrane and ultimately lower permeate salinity.
Figure 13 shows the variation in water production under the three scenarios simulated, that is, under continuous cooling, without cooling, and under maximum production conditions. This latter scenario uses cooling only when it is predicted to result in greater water production than without cooling. These data are presented for the day in autumn for configuration B1 at Qw = 1 L min1 (Figure 13a) and at Qw = 2 L min1 (Figure 13b). For the lower flow rate, the scenario without cooling yields more permeate water during the early morning and late afternoon hours, but the cooling scenario results in greater permeate production for most of the day. Therefore, a hybrid operation consisting of turning the cooling system on and off is proposed to maximise the generation of electricity and hence maximising the water production. For this case, maximum production would be achieved if the cooling system is engaged only when the increase in energy generation due to the increase in efficiency overcomes the trade-off with energy losses due to pressure drop in the heat exchanger, which occurs roughly between 9:00 h and 15:30 h. On the other hand, for the larger water flow rate, the cooled scenario never overcomes the increased energy losses due to pressure drop, so for that case it is not convenient to engage the cooling system on that particular autumn day.
The data presented in Table 5 and Table 6 and Figure 13 are for simulation results using weather measurements from the autumn and summer seasons. Nonetheless, simulations were also carried out using data from the winter season (3 January 2020). However, the winter simulations indicated less permeate production under forced cooling regardless of the water flow rate. This because the power required to overcome pressure losses in the PVT heat exchanger is larger than the gains in energy production, resulting in less available power for the HP pump. Hence, the winter data are not presented in this paper.

4. Conclusions

The results presented in this paper confirm that it is possible to achieve larger PV energy production as well as more RO permeate by cooling the PV modules using the RO feed water, achieving the expected synergies. However, pumping energy is required to force the flow of cooling water across the heat exchange surface with the PV module, which presents a trade-off that limits the conditions under which it is advisable to operate this cooling. This because the efficiency gains may not be sufficient to cover the required pumping energy, resulting in less energy available to operate the RO unit despite larger energy generation by the PV module.
The results of the statistical analysis of the operating parameters for the PVT-RO system yield some insights into the characteristics of the proposed cooling configurations that result in greater electrical efficiency gains. The main objective of the forced convective cooling through heat exchange should be to remove as much thermal energy as possible without incurring in significant efficiency drop due to a non-uniform temperature distribution. Although higher heat transfer coefficients may maximise the efficiency for a particular configuration, this should not be the only consideration.
On the other hand, the way in which the fluid enters the PVT module was seen to be one of the main drivers of efficiency drop, with configurations from group B leading to better performance. This group was characterised by symmetric vertical flow feed and multiple inputs close to each other. This can be related to PV cells being grouped in series by the manufacturer in vertical direction. Moreover, the cooling configurations that presented the best electrical performance were those that forced the fluid to circulate in a continuous direction from inlet to outlet, either horizontal or vertical, preventing recirculation. Future complementary investigations are recommended, in which the implementation of flow channels inside the heat exchanger is contemplated, as well as the optimisation of cooling water flow rate.
In addition, the PVT water outlet temperature was shown to influence the RO system, so it is imperative to consider the PVT-RO system as a whole when selecting the cooling configuration to be used. Thus, it can be concluded that out of the configurations tested, the characteristics of the B1 configuration are the best suited for the production of permeate water under the conditions proposed by this study. This configuration resulted in the highest percentage increase in permeate water compared to not using a cooling system, leading to a predicted 16.7% increase in production during summer and a 27% increase in production during autumn, growing to a 27.5% increase in autumn when only engaging the cooling system when the conditions for an increase in production is observed.
Although increasing the cooling water flow rate generally leads to a decrease in efficiency drop in the PV modules, the energy losses due to pressure drop in the heat exchanger also increase substantially, such that the gains in efficiency do not compensate for the energy losses. For this reason, it is recommended to run the system at lower cooling water flow rates. It is important to point out that the present investigation did not determine the optimal water flow rate for the proposed system. Hence, this is an area of opportunity for future studies. Nevertheless, the results are conclusive for lower cooling water flow rates in the ranges of the proposed experiment.
The decrease in rejection and higher permeate salinity when using feed water to cool the PV modules may be a limitation for applications with high salt content, such as seawater RO for which feed salinity is usually around 35,000 ppm. For that application, a relatively low rejection of 92% may lead to an unacceptably high permeate salinity. Therefore, the relevance of PVT-RO should be analysed according to the specific case and need. In addition, for seawater applications the feed osmotic pressure is higher, which would result in a reduction in the number of hours for which the system can be operated due to low energy generation at lower irradiation conditions. Conversely, if longer operating hours are a requirement, a larger capital investment in solar modules or batteries would be required to allow the operation at times of lower solar irradiation. Other potential applications for PV module cooling include pumping bore water in remote locations, for which the slight increase in water temperature may not be a significant issue.
In general, forced convective cooling is more likely to be beneficial under conditions of high solar irradiation (>900 W m−2) and high ambient temperature (>35 °C), such as those experienced in the summer in dry arid regions similar to northwest Mexico. In those regions, it is very likely that cooling will be beneficial for most of the summer daylight hours. However, in the spring and autumn, the times of the day for which cooling is beneficial are reduced, and cooling is basically of negligible use in the winter. As the weather conditions vary significantly with geographic location, a more detailed techno-economic case study that considers expected weather patterns is recommended in order to determine whether this strategy would be economically beneficial for a particular location.

5. Patents

The design of the heat exchanger system used to cool the photovoltaic panel using RO feed water, for the purpose of water desalination, has been filed as a patent application to the Mexican Institute of Intellectual Property (IMPI). This application for intellectual property protection, in the industrial design modality, was received by the local IMPI office on December 19, 2019 and is currently pending assessment.

Author Contributions

Conceptualization, M.F.S.V. and G.A.F.W.; methodology, G.A.F.W. and I.M.S.-T.; software, F.S.S.; validation, M.M.A.-O., G.A.F.W., and I.M.S.-T.; formal analysis, M.F.S.V. and M.M.A.-O.; investigation, M.F.S.V.; resources, G.A.F.W. and I.M.S.-T.; data curation, M.F.S.V.; writing—original draft preparation, M.F.S.V. and F.S.S.; writing—review and editing, all authors; visualization, all authors; supervision, G.A.F.W. and I.M.S.-T.; project administration, G.A.F.W.; funding acquisition, G.A.F.W., I.M.S.-T., and M.M.A.-O. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by CONACYT, grant number PDCPN 2015-1221 and Cátedras Project 2338 and by the Instituto Tecnológico de Sonora through PROFAPI-2019-0068.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The data presented in this study are available in this article.

Acknowledgments

The authors would like to acknowledge funding provided by CONACYT, grant number PDCPN 2015-1221, the Cátedras CONACYT Program (Project 2338), for the support of the PhD scholarship of student number (CVU:651531/Becario:626178/No.Apoyo:473376). We would also like to thank ITSON’s Programa de Fomento y Apoyo a Proyectos de Investigación (PROFAPI-2019-0068) for funding provided for this study.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

VariablesDescriptionUnits
AmMembrane aream2
APVActive area of PVT module m2
ApaArea of the PVT module in contact with the airm2
ApxContact area of PVT module with cooling waterm2
CpwHeat capacity of cooling waterJ kg−1 K−1
DSolute diffusivitym2 s−1
dhHydraulic diameterm
EeUseful electrical energy produced over one day W h
EPVRate of energy input to the PVT moduleW
EwRate of energy input to the cooling waterW
fFanning friction factor-
FFFill factor-
fθAngular dependence of solar absorptance-
GbeamBeam solar irradiationW m−2
GdifDiffuse solar irradiationW m−2
GsTotal solar irradiationW m−2
haWind heat transfer coefficientW m−2 K−1
hchRO membrane feed channel heightm
HoExtraterrestrial radiation on a horizontal surfaceW m−2
HRRelative humidity%
ΔHp,tmTransmembrane pressure-enthalpy changeJ kg−1
ΔHT,tmTransmembrane temperature-enthalpy changeJ kg−1
ΔHs,rSpecific enthalpy change of solution for NaCl at reference conditionsJ kg−1
IscShort-circuit currentA
JvLocal volumetric permeate fluxm s−1
kmtMass transfer coefficient on the membrane surfacem s−1
ktHourly clearness index-
LRO module lengthm
MsMolar mass of NaClkg mol−1
PeElectric power available for the high-presure pumpW
PeoElectric power output from the PVT moduleW
PLPElectric power required by the low-pressure pumpW
pPressure Pa
pbPressure along feed channel fluid in RO modulePa
ppPermeate pressurePa
ΔpPVTPressure drop across the PVT heat exchangerPa
ΔptmTransmembrane pressure differencePa
PrPrandtl number-
QbVolumetric flow rate in the feed channel of the RO modulem3 s−1
QpVolumetric flow rate of RO permeatem3 s−1, L min−1
QwCooling water volumetric flow ratem3 s−1, L min−1
qaRate of heat removal from the PVT module by convective heat transfer with the windW
qrRate of heat removal from the PVT module radiative heat transfer with the skyW
qsRate of solar energy absorption by the PVT moduleW
qwRate of heat removal from the PVT module by forced convection with cooling waterW
qxHeat exchanged between PVT module and cooling waterW
RgUniversal gas constantJ mol−1 K−1
RintRO membrane intrinsic salt rejection-
RmHydraulic resistance of RO membranem−1
RobsObserved salt rejection for RO membrane module-
ReReynolds number-
ScSchmidt number-
ShSherwood number-
TTemperature°C, K
TaAmbient temperature°C, K
TbTemperature along feed channel in RO module°C, K
TdpDew point temperature°C
TPVPV module temperature°C, K
TPV,maxMaximum PV module temperature°C
TrReference temperature°C
TskySky temperatureK
TwiTemperature of cooling water at PVT module inlet°C
TwoTemperature of cooling water at PVT module outlet°C
ΔTlmLogarithmic mean temperature difference between PV module and cooling waterK
UOverall heat transfer coefficient for cooling water heat exchangeW m−2 K
ubBulk feed flow velocity in membrane modulem s−1
VVoltageV
vaWind speedm s−1
VocOpen-circuit voltageV
VolpPermeate volume produced over one daym3
WPowerW
wbSalinity mass fraction along feed channel fluid in RO module-
wpSalinity mass fraction of RO permeate-
Greek SymbolsDescriptionUnits
αPV module solar absorptivity-
βAngle of incidence between the solar beam irradiation and the horizontal plane°
ГConcentration polarisation modulus-
εPV module emissivity-
ϵVoid fraction in feed channel of RO module-
ηEfficiency drop of PVT module%
ηElectrical efficiency of PVT module%
ηcElectrical efficiency of PVT module under forced convective cooling%
ηLPEnergy efficiency of the low-pressure pump%
ηuElectrical efficiency of PV module at uniform temperature%
φOsmotic coefficient-
μFluid viscosityPa s
πmOsmotic pressure on the feed side of the RO membrane surfacePa
πpOsmotic pressure on the permeate side of the RO membrane surfacePa
θAngle of incidence between the solar beam irradiation and the PV module°
ρDensitykg m−3
ρpDensity of the RO permeatekg m−3
ρwDensity of waterkg m−3
σStefan-Boltzmann constant W m−2 K−4
σTStandard deviation of the PV module temperature distributionK

Abbreviations

AOscilloscope current sensing probe
CCapacitor
HPHigh-pressure
LPLow-pressure
ODEOrdinary differential equation
PVPhotovoltaic
PVCPolyvinyl chloride
PVTPhotovoltaic-thermal
RResistor
ROReverse osmosis
SW1Load capacitor switch 1
SW2Load resistor switch 2
VOscilloscope voltage sensing probe

Appendix A

This section presents thermographic images for each of the heat exchange configurations tested in this work, as well as schematic depiction of the expected flow lines. These are presented in Figure A1 for group B, in Figure A2 for group S, and in Figure A3 for group L. The images show areas with temperatures ranging from 25 to 69 °C. However, a scale with a temperature range of 30 to 45 °C is used to better visualise this range with a wider colour scale.
Figure A1. Diagrams of expected flow lines for group B configurations, alongside their respective thermographic images. The reader is referred to Table 2 for the description of each configuration.
Figure A1. Diagrams of expected flow lines for group B configurations, alongside their respective thermographic images. The reader is referred to Table 2 for the description of each configuration.
Water 13 00229 g0a1
Figure A2. Diagrams of expected flow lines for group S configurations, alongside their respective thermographic images. The reader is referred to Table 2 for the description of each configuration.
Figure A2. Diagrams of expected flow lines for group S configurations, alongside their respective thermographic images. The reader is referred to Table 2 for the description of each configuration.
Water 13 00229 g0a2
Figure A3. Diagrams of expected flow lines for group L configurations, alongside their respective thermographic images. The reader is referred to Table 2 for the description of each configuration.
Figure A3. Diagrams of expected flow lines for group L configurations, alongside their respective thermographic images. The reader is referred to Table 2 for the description of each configuration.
Water 13 00229 g0a3

Appendix B

This section presents the characteristic curve of the low-pressure (LP) pump used in the experiments for circulating feed water through the different heat exchange configurations tested in this paper. The curve presented in Figure A4 is used to determine the pressure drop across the PVT module and to determine the pumping energy requirements for a fit-for-purpose pump in the simulated PVT-RO system.
Figure A4. Experimental low-pressure pump characteristic curve.
Figure A4. Experimental low-pressure pump characteristic curve.
Water 13 00229 g0a4
The pressure drop in the PVT heat exchanger (ΔpPVT) is taken to be equal to the dynamic head supplied to the fluid by the experimental LP pump, multiplied by the gravitational acceleration and the density of the cooling water (ρw). Because the volumetric flow rate through the experimental LP pump is not easily controlled, the volumetric flow rate of cooling water through the PVT module (Qw) was manipulated using a bypass valve after the LP pump outlet, with the bypass flow returning to the feed tank. Therefore, the total flow rate through the experimental LP pump (i.e., the sum of Qw and the bypass flow) is used to determine the dynamic head from Figure A4, and this value is used to estimate ΔpPVT. This approach is followed for all the cooling configurations tested in this work.

Appendix C

This section presents and summarises the auxiliary equations required for the PVT-RO modelling described in Section 2.4.
The mathematical model for the high-pressure (HP) pump calculates the voltage and maximum output pressure, for a given volumetric flow rate operating condition and the electrical power available from the solar PVT module. This calculation is based on the technical datasheet of a HP DC pump (SunPumps SIJ 3.1-1500P-225 BL) which is capable of operating under the conditions necessary for brackish water RO. The technical data for the pump are fitted to a multilinear model of the form:
[ p V p u m p ] = [ a 0 , 1 a 1 , 1 a 2 , 1 a 0 , 2 a 1 , 2 a 2 , 2 a 3 , 1 a 4 , 1 a 5 , 1 a 3 , 2 a 4 , 2 a 5 , 2 ] [ 1 Q w Q w 2 P e P e 2 Q w P e ]
where p is the fluid outlet pressure in psi, Vpump is the voltage required by the pump in V, Qw is the volumetric flow rate L min−1, and Pe and is the electrical power available in W. The values of the coefficients for this multilinear fit are given in Table A1.
Table A1. Coefficient values for the multilinear regression in Equation (A1).
Table A1. Coefficient values for the multilinear regression in Equation (A1).
CoefficientValue
a0,1−301.03
a1,135.872
a2,1−2.6886
a3,11.4446
a4,1−1.75 × 10−5
a5,1−6.5214 × 10−2
a0,2105.90
a1,2−6.6648
a2,21.2169
a3,21.2325 × 10−2
a4,21.24 × 10−7
a5,2−1.1288 × 10−4
The logarithmic mean temperature difference between the PV module and the cooling water (ΔTlm) used in Equations (3) and (4) is given by:
Δ T l m = T w o T w i ln ( T P V T w i T P V T w o )
For the experiments described in Section 2.3, solar irradiation (Gs) data are obtained from pyranometer measurements. However, the pyranometer measures the solar radiation on a horizontal plane. Therefore, assuming that the angle of incidence between the solar beam irradiation (Gbeam) and the horizontal plane is β, the following holds:
G b e a m = G s G d i f cos β
Diffuse irradiation (Gdif) in Equations (7) and (A3) is estimated as proposed by Boland et al. [35]:
G d i f = G s 1 + exp ( 5.03 + 8.6 k t )
where kt is the hourly clearness index, defined in terms of the extraterrestrial radiation on a horizontal surface (H0):
k t = G s H 0
The value of H0 depends on the month of the year in question [27,36]. The angular dependence of solar absorptance (fθ) in Equation (7) is given by [27]:
f θ = 1 1.59 × 10 3 θ + 2.73 × 10 4 θ 2 2.3 × 10 5 θ 3 + 9.02 × 10 7 θ 4 1.8 × 10 8 θ 5 + 1.77 × 10 10 θ 6 + 6.99 × 10 13 θ 7
where θ is the incidence angle between the solar PV module and the solar beam irradiation, in degrees.
The wind heat transfer coefficient (ha) in Equation (8) is given by [27]:
h a = 5.7 + 3.8 v a
where ha is given in W m−2 K−1, and va in m s−1.
The sky temperature (Tsky) in Equation (9) is given by [27]:
T s k y = T a { 0.71 + 0.0056 T d p + 7.3 × 10 5 T d p 2 + 0.013 cos [ 15 π ( t 12 ) 180 ] } 1 / 4
where Tsky and Ta are in K, Tdp is the dew point temperature in °C, and t is the time of the day in hours since midnight.
The dew point temperature (Tdp) in Equation (A8) can be obtained using Antoine equation parameters for the vapour pressure of water, such that:
T d p = [ 1 T a + C log 10 R H 2 B ] 1 C
where Tdp and Ta are in °C, RH is given as a percentage, and the coefficient values for water vapour are B = 1730.63 and C = 233.426 [37].
The mass transfer coefficient in Equation (17) depends on the geometry and flow conditions inside the membrane module, and can be obtained from empirical equations that correlate the Reynolds (Re) and Schmidt (Sc) numbers to the Sherwood number (Sh). Schock and Miquel [33] give the following correlation for typical RO spacer-filled (FilmTec) spiral wound membrane module:
S h = 0.065 R e 0.875 S c 0.25
where the dimensionless numbers are defined as:
R e = ρ u b d h ϵ μ
S c = μ ρ D
S h = k m t d h D
where D is the solute diffusivity. The bulk fluid velocity in the feed channel of the RO module is defined as:
u b = Q b L h c h A m
where Am is the membrane area and L is the RO module length.
The membrane resistance (Rm) in Equation (15) is slightly temperature dependent and can be determined from DI water permeation data by varying the feed pressure, a process that is widely reported in the literature [38,39,40]. This process is repeated for several temperature values, and Rm is then fitted to a linear dependency on temperature based on experimental data:
R m = 3.9598 × 10 14 1.0976 × 10 12 T b  
where Tb is given in K, and Rm is given in m−1. This fit was obtained experimentally for the particular membrane modelled, which in the case of this paper is a BW30 (DuPont) TFC RO membrane.
Salt passage through the membrane is modelled using the membrane intrinsic rejection, defined in terms of the salinity mass fraction on either side of the membrane, that is:
R i n t = w m w p w m  
On the other hand, the observed rejection (Robs) in Equations (19) and (20) is defined in terms of the bulk and permeate salinity mass fractions, that is:
R o b s = w b w p w b  
These two rejection definitions are related through the concentration polarisation modulus:
Γ = ( 1 R o b s R o b s ) ( R i n t 1 R i n t )  
Similarly to membrane resistance, intrinsic rejection is also slightly temperature dependent. This relationship is determined experimentally for several temperature and salinity values, and Rint is then fitted to a linear dependency on temperature based on the experimental data:
R i n t = 0.99976 1.487 × 10 4 T b  
where Tb is given in °C.

Appendix D

This section presents the weather data sets used for the prediction of permeate water production for the proposed PVT-RO system, as well as the resulting simulated average PVT outlet water temperatures. The input data were sourced from a local weather station in Ciudad Obregon, Mexico (27°29′35.2″ N 109°58′10.7″ W). These data are presented in Table A2 for summer conditions (24 July 2018), in Table A3 for autumn conditions (20 October 2019), and in Table A4 for winter conditions (3 January 2020).
Table A2. Weather data set for the summer day (24 July 2018) used in the PVT-RO simulations.
Table A2. Weather data set for the summer day (24 July 2018) used in the PVT-RO simulations.
Time of Day
(h)
Gs
(W m−2)
HR
(%)
Ta
(°C)
va
(m s−1)
6–7316.6657.0731.711.491
7–8528.3347.8133.651.574
8–9715.0041.8535.111.542
9–10853.3335.3336.741.238
10–11936.6638.3737.111.395
11–12973.3337.5237.431.283
12–13936.6629.9438.531.059
13–14836.6627.3638.971.113
14–15686.6626.4739.480.959
15–16495.0030.7938.960.995
16–17275.0038.0637.161.112
Table A3. Weather data set for the autumn day (20 October 2019) used in the PVT-RO simulations.
Table A3. Weather data set for the autumn day (20 October 2019) used in the PVT-RO simulations.
Time of Day
(h)
Gs
(W m−2)
HR
(%)
Ta
(°C)
va
(m s−1)
6–74.8382.1121.500.000
7–8132.1679.2622.470.041
8–9358.3366.8724.990.403
9–10553.3356.1027.070.973
10–11702.6648.4028.901.120
11–12785.0039.2931.040.809
12–13805.6635.1032.111.118
13–14756.3333.1732.600.871
14–15646.5030.5833.550.908
15–16473.8330.5433.441.286
16–17226.0036.0032.311.540
17–1822.8341.0830.171.508
Table A4. Weather data set for the winter day (3 January 2020) used in the PVT-RO simulations.
Table A4. Weather data set for the winter day (3 January 2020) used in the PVT-RO simulations.
Time of Day
(h)
Gs
(W m−2)
HR
(%)
Ta
(°C)
va
(m s−1)
6–70.0087.6610.040.000
7–89.5088.059.870.000
8–9143.0087.5110.750.211
9–10373.0078.9613.241.517
10–11534.1665.6416.161.259
11–12644.0051.7818.581.302
12–13685.6641.6120.651.363
13–14660.1632.7121.761.246
14–15569.0026.2522.571.246
15–16412.3324.6723.191.042
16–17186.6624.4222.911.193
17–1811.0038.2320.590.869
Table A5 shows the effect of the PVT module configuration on the temperature of the cooling water exiting the module. The inlet water temperatures are 28.7 °C and 20 °C on 24 July 2018 and 20 October 2019, respectively. The water temperatures for 3 January 2020 are not included as implementing cooling on that day did not result in increased permeate production for the PVT-RO system.
Table A5. Average outlet water temperatures by PVT module configuration and cooling water volumetric flow rate.
Table A5. Average outlet water temperatures by PVT module configuration and cooling water volumetric flow rate.
ConfigurationCooling Water Flow Rate, Qw (L min−1)
1212
PVT Average Outlet Water Temperature, Two (°C)
24 July 201820 October 2019
B135.8 ± 2.732.1 ± 1.326.3 ± 2.422.6 ± 1.4
B232.9 ± 1.630.6 ± 0.723.3 ± 1.721.5 ± 0.8
B333.8 ± 2.031.6 ± 1.124.0 ± 2.122.3 ± 1.2
B432.1 ± 1.331.3 ± 1.022.7 ± 1.422.1 ± 1.1
B533.0 ± 1.731.1 ± 0.923.4 ± 1.821.9 ± 1.0
S132.8 ± 1.631.1 ± 0.923.3 ± 1.721.9 ± 1.0
S234.1 ± 2.131.7 ± 1.124.2 ± 2.222.3 ± 1.2
S332.3 ± 1.431.4 ± 1.122.9 ± 1.522.2 ± 1.4
L134.5 ± 2.232.3 ± 1.424.6 ± 2.322.8 ± 1.4
L232.8 ± 1.631.6 ± 1.123.3 ± 1.722.3 ± 1.2
L332.3 ± 1.431.1 ± 0.922.9 ± 1.521.9 ± 1.0

References

  1. Pandey, V.P.; Shrestha, S. Evolution of the nexus as a policy and development discourse. Water-Energy-Food Nexus Princ. Pract. 2017, 1, 11–20. [Google Scholar] [CrossRef]
  2. Cairns, R.; Krzywoszynska, A. Anatomy of a buzzword: The emergence of ‘the water-energy-food nexus’ in UK natural resource debates. Environ. Sci. Policy 2016, 64, 164–170. [Google Scholar] [CrossRef]
  3. Armendáriz-Ontiveros, M.M.; Álvarez-Sánchez, J.; Dévora-Isiordia, G.E.; García, A.; Fimbres Weihs, G.A. Effect of seawater variability on endemic bacterial biofouling of a reverse osmosis membrane coated with iron nanoparticles (FeNPs). Chem. Eng. Sci. 2020, 223, 115753. [Google Scholar] [CrossRef]
  4. Cherif, H.; Belhadj, J. Environmental Life Cycle Analysis of Water Desalination Processes. In Sustainable Desalination Handbook; Elsevier: Amsterdam, The Netherlands, 2018; pp. 527–559. [Google Scholar] [CrossRef]
  5. Leijon, J.; Salar, D.; Engström, J.; Leijon, M.; Boström, C. Variable renewable energy sources for powering reverse osmosis desalination, with a case study of wave powered desalination for Kilifi, Kenya. Desalination 2020, 494, 114669. [Google Scholar] [CrossRef]
  6. Khan, M.A.M.; Rehman, S.; Al-Sulaiman, F.A. A hybrid renewable energy system as a potential energy source for water desalination using reverse osmosis: A review. Renew. Sustain. Energy Rev. 2018, 97, 456–477. [Google Scholar] [CrossRef]
  7. Eltawil, M.A.; Zhengming, Z.; Yuan, L. A review of renewable energy technologies integrated with desalination systems. Renew. Sustain. Energy Rev. 2009, 13, 2245–2262. [Google Scholar] [CrossRef]
  8. Rezk, H.; Sayed, E.T.; Al-Dhaifallah, M.; Obaid, M.; El-Sayed, A.H.M.; Abdelkareem, M.A.; Olabi, A.G. Fuel cell as an effective energy storage in reverse osmosis desalination plant powered by photovoltaic system. Energy 2019, 175, 423–433. [Google Scholar] [CrossRef] [Green Version]
  9. Elmaadawy, K.; Kotb, K.M.; Elkadeem, M.R.; Sharshir, S.W.; Dán, A.; Moawad, A.; Liu, B. Optimal sizing and techno-enviro-economic feasibility assessment of large-scale reverse osmosis desalination powered with hybrid renewable energy sources. Energy Convers. Manag. 2020, 224, 113377. [Google Scholar] [CrossRef]
  10. Mostafaeipour, A.; Qolipour, M.; Rezaei, M.; Babaee-Tirkolaee, E. Investigation of off-grid photovoltaic systems for a reverse osmosis desalination system: A case study. Desalination 2019, 454, 91–103. [Google Scholar] [CrossRef]
  11. Schies, A.; Went, J.; Heidtmann, C.; Eisele, M.; Kroemke, F.; Schmoch, H.; Vetter, M. Operating control strategies and dimensioning of photovoltaic powered reverse osmosis desalination plants without batteries. Desalination Water Treat. 2010, 21, 131–137. [Google Scholar] [CrossRef]
  12. Raval, H.D.; Maiti, S. Ultra-low energy reverse osmosis with thermal energy recovery from photovoltaic panel cooling and TFC RO membrane modification. Desalination Water Treat. 2016, 57, 4303–4312. [Google Scholar] [CrossRef]
  13. Siecker, J.; Kusakana, K.; Numbi, B. A review of solar photovoltaic systems cooling technologies. Renew. Sustain. Energy Rev. 2017, 79, 192–203. [Google Scholar] [CrossRef]
  14. Luque, A.; Sala, G.; Arboiro, J. Electric and thermal model for non-uniformly illuminated concentration cells. Sol. Energy Mater. Sol. Cells 1998, 51, 269–290. [Google Scholar] [CrossRef]
  15. Royne, A.; Dey, C.J.; Mills, D.R. Cooling of photovoltaic cells under concentrated illumination: A critical review. Sol. Energy Mater. Sol. Cells 2005, 86, 451–483. [Google Scholar] [CrossRef]
  16. Bahaidarah, H.M.; Baloch, A.A.; Gandhidasan, P. Uniform cooling of photovoltaic panels: A review. Renew. Sustain. Energy Rev. 2016, 57, 1520–1544. [Google Scholar] [CrossRef]
  17. Zhang, C.; Shen, C.; Wei, S.; Wang, Y.; Lv, G.; Sun, C. A review on recent development of cooling technologies for photovoltaic modules. J. Therm. Sci. 2020, 29, 1410–1430. [Google Scholar] [CrossRef]
  18. Raval, H.D.; Maiti, S.; Mittal, A. Computational fluid dynamics analysis and experimental validation of improvement in overall energy efficiency of a solar photovoltaic panel by thermal energy recovery. J. Renew. Sustain. Energy 2014, 6, 033138. [Google Scholar] [CrossRef]
  19. Jin, X.; Jawor, A.; Kim, S.; Hoek, E.M.V. Effects of feed water temperature on separation performance and organic fouling of brackish water RO membranes. Desalination 2009, 239, 346–359. [Google Scholar] [CrossRef]
  20. Monjezi, A.A.; Chen, Y.; Vepa, R.; Kashyout, A.E.-H.B.; Hassan, G.; Fath, H.E.-B.; Kassem, A.E.-W.; Shaheed, M.H. Development of an off-grid solar energy powered reverse osmosis desalination system for continuous production of freshwater with integrated photovoltaic thermal (PVT) cooling. Desalination 2020, 495, 114679. [Google Scholar] [CrossRef]
  21. Spertino, F.; Ahmad, J.; Ciocia, A.; Di Leo, P.; Murtaza, A.F.; Chiaberge, M. Capacitor charging method for I–V curve tracer and MPPT in photovoltaic systems. Sol. Energy 2015, 119, 461–473. [Google Scholar] [CrossRef] [Green Version]
  22. Sharqawy, M.H.; Lienhard, J.H.; Zubair, S.M. Thermophysical properties of seawater: A review of existing correlations and data. Desalination Water Treat. 2010, 16, 354–380. [Google Scholar] [CrossRef]
  23. Sun, H.; Feistel, R.; Koch, M.; Markoe, A. New equations for density, entropy, heat capacity, and potential temperature of a saline thermal fluid. Deep Sea Res. Part I Oceanogr. Res. Pap. 2008, 55, 1304–1310. [Google Scholar] [CrossRef]
  24. Isdale, J.D.; Morris, R. Physical properties of sea water solutions: Density. Desalination 1972, 10, 329–339. [Google Scholar] [CrossRef]
  25. Gosset, E. Another differences calculus based on standar desviation and confidence interval. Stat. Ref. 1917, 26, 66–72. [Google Scholar]
  26. Kaiser, H.F. An index of factorial simplicity. Psychometrika 1974, 39, 31–36. [Google Scholar] [CrossRef]
  27. Duffie, J.A.; Beckman, W.A. Solar Engineering of Thermal Processes, 4th ed.; Wiley: Hoboken, NJ, USA, 2013. [Google Scholar]
  28. Toh, K.Y.; Liang, Y.Y.; Lau, W.J.; Fimbres Weihs, G.A. The techno-economic case for coupling advanced spacers to high-permeance RO membranes for desalination. Desalination 2020, 491, 114534. [Google Scholar] [CrossRef]
  29. Bartholomew, T.V.; Mauter, M.S. Computational framework for modeling membrane processes without process and solution property simplifications. J. Membr. Sci. 2019, 573, 682–693. [Google Scholar] [CrossRef]
  30. Chapra, S.C.; Canale, R.P. Numerical Methods for Engineers, 6th ed.; McGraw-Hill: New York, NY, USA, 2010; p. 968. [Google Scholar]
  31. Kedem, O.; Katchalsky, A. Thermodynamic Analysis of the Permeability of Biological Membranes to Non-Electrolytes. Biochim. Biophys. Acta 1958, 27, 229. [Google Scholar] [CrossRef]
  32. FILMTEC. FILMTEC 8” Brackish Water RO Element Specifications. In Product Information; FilmTec Corporation, Ed.; FILMTEC: Minneapolis, MN, USA, 1988; Volume 609-00616-0808. [Google Scholar]
  33. Schock, G.; Miquel, A. Mass transfer and pressure loss in spiral wound modules. Desalination 1987, 64, 339–352. [Google Scholar] [CrossRef]
  34. Sivertsen, E.; Holt, T.; Thelin, W.R. Concentration and Temperature Effects on Water and Salt Permeabilities in Osmosis and Implications in Pressure-Retarded Osmosis. Membranes 2018, 8, 39. [Google Scholar] [CrossRef] [Green Version]
  35. Boland, J.; Ridley, B.; Brown, B. Models of diffuse solar radiation. Renew. Energy 2008, 33, 575–584. [Google Scholar] [CrossRef]
  36. Ridley, B.; Boland, J.; Lauret, P. Modelling of diffuse solar fraction with multiple predictors. Renew. Energy 2010, 35, 478–483. [Google Scholar] [CrossRef]
  37. Reid, R.C.; Prausnitz, J.M.; Sherwood, T.K. The Properties of Gases and Liquids, 3rd ed.; McGraw-Hill: New York, NY, USA, 1997. [Google Scholar]
  38. Chong, T.H.; Wong, F.S.; Fane, A.G. Enhanced concentration polarization by unstirred fouling layers in reverse osmosis: Detection by sodium chloride tracer response technique. J. Membr. Sci. 2007, 287, 198–210. [Google Scholar] [CrossRef]
  39. Armendáriz-Ontiveros, M.M.; García García, A.; de los Santos Villalobos, S.; Fimbres Weihs, G.A. Biofouling performance of RO membranes coated with Iron NPs on graphene oxide. Desalination 2019, 451, 45–58. [Google Scholar] [CrossRef]
  40. Liang, Y.Y.; Fimbres Weihs, G.A.; Wiley, D.E. Comparison of oscillating flow and slip velocity mass transfer enhancement in spacer-filled membrane channels: CFD analysis and validation. J. Membr. Sci. 2020, 593, 117433. [Google Scholar] [CrossRef]
Figure 1. Arrangement of PV cells in PV module.
Figure 1. Arrangement of PV cells in PV module.
Water 13 00229 g001
Figure 2. PV Module I-V curve extraction circuit. Ipv: PV module current, Vpv: PV Module voltage, SW1: Load capacitor switch 1, SW2: Load resistor switch 2, A: Oscilloscope Current sensing probe, V: Oscilloscope voltage sensing probe, C: Capacitor load, R: Resistor load.
Figure 2. PV Module I-V curve extraction circuit. Ipv: PV module current, Vpv: PV Module voltage, SW1: Load capacitor switch 1, SW2: Load resistor switch 2, A: Oscilloscope Current sensing probe, V: Oscilloscope voltage sensing probe, C: Capacitor load, R: Resistor load.
Water 13 00229 g002
Figure 3. Constructed PVT heat exchanger indicating valve locations: (a) Schematic diagram, (b) Photograph of the experimental PVT module.
Figure 3. Constructed PVT heat exchanger indicating valve locations: (a) Schematic diagram, (b) Photograph of the experimental PVT module.
Water 13 00229 g003
Figure 4. Schematic of heat exchange configuration B4, with inlets and outlets indicated by white arrows and expected flow lines (not calculated) indicated by black arrows.
Figure 4. Schematic of heat exchange configuration B4, with inlets and outlets indicated by white arrows and expected flow lines (not calculated) indicated by black arrows.
Water 13 00229 g004
Figure 5. Experimental setup: (a) photograph, (b) schematic.
Figure 5. Experimental setup: (a) photograph, (b) schematic.
Water 13 00229 g005
Figure 6. Schematic diagram of the PVT-RO system.
Figure 6. Schematic diagram of the PVT-RO system.
Water 13 00229 g006
Figure 7. Variable map and block diagram of the mathematical model of the PVT-RO system, where green arrows are inputs, black arrows are intermediate variables, and red arrows are outputs. Refer to the nomenclature for variable descriptions.
Figure 7. Variable map and block diagram of the mathematical model of the PVT-RO system, where green arrows are inputs, black arrows are intermediate variables, and red arrows are outputs. Refer to the nomenclature for variable descriptions.
Water 13 00229 g007
Figure 8. Schematic diagram of the unidimensional RO model, showing inputs, outputs and profile variables. Refer to the nomenclature for variable descriptions.
Figure 8. Schematic diagram of the unidimensional RO model, showing inputs, outputs and profile variables. Refer to the nomenclature for variable descriptions.
Water 13 00229 g008
Figure 9. Measured I-V curve at TPV = 59.2 °C and Gs = 1000 W m−2, for the PV modules used in this work.
Figure 9. Measured I-V curve at TPV = 59.2 °C and Gs = 1000 W m−2, for the PV modules used in this work.
Water 13 00229 g009
Figure 10. Effect of temperature on efficiency for the PV module.
Figure 10. Effect of temperature on efficiency for the PV module.
Water 13 00229 g010
Figure 11. Ranges of observed normalised temperatures for each heat exchange configuration, with the median and quartiles indicated.
Figure 11. Ranges of observed normalised temperatures for each heat exchange configuration, with the median and quartiles indicated.
Water 13 00229 g011
Figure 12. Effect on the efficiency drop (Δη) of: (a) maximum PV module temperature (TPV,max), (b) overall heat transfer coefficient (U), and (c) standard deviation of temperature distribution (σT). Data points for the same configuration are joined by a line, with the unmarked ends of the lines representing the data at Qw = 1 L min−1, and the ends marked with a circle representing the data at Qw = 2 L min−1.
Figure 12. Effect on the efficiency drop (Δη) of: (a) maximum PV module temperature (TPV,max), (b) overall heat transfer coefficient (U), and (c) standard deviation of temperature distribution (σT). Data points for the same configuration are joined by a line, with the unmarked ends of the lines representing the data at Qw = 1 L min−1, and the ends marked with a circle representing the data at Qw = 2 L min−1.
Water 13 00229 g012
Figure 13. Simulated daily water generation for 20 October 2019, using configuration B1 at: (a) Qw = 1 L min1; (b) Qw = 2 L min1.
Figure 13. Simulated daily water generation for 20 October 2019, using configuration B1 at: (a) Qw = 1 L min1; (b) Qw = 2 L min1.
Water 13 00229 g013
Table 1. Electrical generation properties for the AXITEC AC-270-P modules at standard test conditions.
Table 1. Electrical generation properties for the AXITEC AC-270-P modules at standard test conditions.
ParameterValueUnits
Rated power270W
Rated voltage31.12V
Rated current8.71A
Short circuit current (Icc)9.25A
Open circuit voltage (Voc)38.21V
Efficiency (η)16.60%
Fill factor (FF)0.766-
Dimensions1640 × 992 × 35mm
Effective area (APV)1.47m2
Operating temperature−40 to 85°C
Table 2. Description of each of the heat exchange configurations analysed.
Table 2. Description of each of the heat exchange configurations analysed.
ConfigurationInlet (s)Outlet (s)
B11, 2, 3, 4, 12, 13, 145, 11
B21, 2, 3, 4, 12, 13, 148
B31, 2, 3, 4, 12, 13, 146, 7, 9, 10
B41, 2, 3, 4, 12, 13, 1415, 16
B51, 2, 3, 4, 12, 13, 149, 10
S13, 415, 16
S2215, 16
S36, 79, 10
L13, 41, 9, 10, 11, 12
L2113, 4, 5, 6, 7
L31, 9, 10, 11, 123, 4, 5, 6, 7
Table 3. Simulated PVT-RO unit dimensions and characteristics.
Table 3. Simulated PVT-RO unit dimensions and characteristics.
ParameterValueUnits
Membrane length [32]0.955m
Membrane area [32]2.8m2
Feed channel height (hch) [33]0.77mm
Feed channel void fraction ( ϵ ) [33]0.89mm
Feed channel hydraulic diameter (dh) [33]0.95mm
PV module area (Ap)1.52m2
Cooling water film thickness0.027m
Cooling water inlet temperature (Twi)25°C
Number of PVT modules4modules
Cooling water inlet salinity (wb)500ppm
Total water flow (Qb)8L min1
Table 4. Pearson correlation coefficients between efficiency drop (Δη) and each of the studied input parameters, for each configuration and for the overall data set. Highly significant correlation coefficients are highlighted in bold.
Table 4. Pearson correlation coefficients between efficiency drop (Δη) and each of the studied input parameters, for each configuration and for the overall data set. Highly significant correlation coefficients are highlighted in bold.
Pearson Correlation Coefficient between Δη and:
ConfigurationQwUσTTPV,max
B1−0.570.67−0.27−0.82
B2−0.500.310.590.58
B3−0.620.050.700.83
B4−0.73−0.50−0.45−0.40
B5−0.31−0.68−0.29−0.28
S1−0.83−0.46−0.34−0.15
S2−0.93−0.220.210.04
S3−0.35−0.680.530.31
L1−0.51−0.200.640.52
L2−0.79−0.670.160.40
L3−0.48−0.18−0.920.90
Overall−0.10−0.070.180.22
Table 5. Simulation results for PVT-RO hybrid system power generation and water production, based on weather data for 20 October 2019.
Table 5. Simulation results for PVT-RO hybrid system power generation and water production, based on weather data for 20 October 2019.
ScenarioVolp
(m3)
Ee
(Wh)
wp
(ppm)
Volp
(m3)
Ee
(Wh)
wp
(ppm)
Volp
(m3)
Increase
(%)
Volp
(m3)
Increase
(%)
WithoutCooling1.2968844.3
ScenarioContinuous CoolingMax Production
Qw1 L min12 L min11 L min12 L min1
B11.6509138.41.0026368.11.65027.5%1.296-
B21.4528796.20.8346036.31.45812.6%1.296-
B31.5068886.80.9366227.21.50616.4%1.296-
B41.4048725.80.9066146.91.4109.2%1.296-
B51.4408756.30.8886176.81.44011.5%1.296-
S11.4108696.10.9066276.81.4169.7%1.296-
S21.5128887.00.9666357.21.51817.3%1.296-
S31.4228746.00.9306267.01.42810.5%1.296-
L11.5128827.11.0266497.81.51217.0%1.296-
L21.3988666.10.9546347.21.4109.0%1.296-
L31.3568575.80.8826186.81.3685.9%1.296-
Table 6. Simulation results for PVT-RO hybrid system power generation and water production, based on weather data for 24 July 2018.
Table 6. Simulation results for PVT-RO hybrid system power generation and water production, based on weather data for 24 July 2018.
ScenarioVolp
(m3)
Ee
(Wh)
wp
(ppm)
Volp
(m3)
Ee
(Wh)
wp
(ppm)
Volp
(m3)
Increase
(%)
Volp
(m3)
Increase
(%)
Without Cooling2.784124720.4
ScenarioContinuous CoolingMax Production
Qw1 L min12 L min11 L min12 L min1
B13.240133639.42.508105423.13.24016.5%2.8381.9%
B23.000126530.42.14898316.83.0068.2%2.784-
B33.066128132.92.352101719.73.07810.6%2.784-
B42.958126129.22.304101019.32.9706.8%2.784-
B52.988126030.02.256100218.22.9947.8%2.784-
S12.958125229.02.286101218.52.9767.0%2.784-
S23.096129334.72.430104121.43.10211.6%2.7900.3%
S33.054130636.42.454105423.13.06610.1%2.8141.3%
L13.060126931.62.478104120.83.07210.4%2.8081.0%
L22.934124227.72.352101919.22.9466.0%2.7840.0%
L32.850121824.52.18498616.72.8743.4%2.784-
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Suzuki Valenzuela, M.F.; Sánchez Soto, F.; Armendáriz-Ontiveros, M.M.; Sosa-Tinoco, I.M.; Fimbres Weihs, G.A. Improving Thermal Distribution in Water-Cooled PV Modules and Its Effect on RO Permeate Recovery. Water 2021, 13, 229. https://doi.org/10.3390/w13020229

AMA Style

Suzuki Valenzuela MF, Sánchez Soto F, Armendáriz-Ontiveros MM, Sosa-Tinoco IM, Fimbres Weihs GA. Improving Thermal Distribution in Water-Cooled PV Modules and Its Effect on RO Permeate Recovery. Water. 2021; 13(2):229. https://doi.org/10.3390/w13020229

Chicago/Turabian Style

Suzuki Valenzuela, Mario F., Fernando Sánchez Soto, María Magdalena Armendáriz-Ontiveros, Ian M. Sosa-Tinoco, and Gustavo A. Fimbres Weihs. 2021. "Improving Thermal Distribution in Water-Cooled PV Modules and Its Effect on RO Permeate Recovery" Water 13, no. 2: 229. https://doi.org/10.3390/w13020229

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop